2021-06-03 10:14:35CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) FEEDER FROM EXISTING 100 AMPS MAIN BREAKER TO NEW
 100 AMPS PANEL IS SHOWN AS 3#2 AL. AMPACITY OF #2 AL IS
 90 AMPS AND AS PER NEC 240.4(B)(2) THE MAXIMUM
 OVERCURRENT DEVICE
 FOR THIS CONDUCTOR IS 90 AMPS (90 AMPS IS AN STANDARD
 BREAKER SIZE). PLEASE INCREASE SIZE OF CONDUCTOR TO
 COMPLY WITH NEC 240.4(B)
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER
 DEVELOPMENT SERVICES
 CITY OF WEST PAM BEACH
 401 CLEMATIS STREET, 1ST FLOOR
 WEST PALM BEACH, FL 33401
  
 FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS,
 561-805-6746.
  