Plan Review Notes
Plan Review Notes For Permit 21050138
Permit Number 21050138
Review Stop B
Sequence Number 2
Notes
Date Text
2021-06-01 12:32:44JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR EMAIL [email protected] AND REQUEST
 THAT IT BE CONVERTED TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL2533-R24 COVERS MULTIPLE ROOF SYSTEMS FOR
 WOOD DECKS; SYSTEM NO. W-1 THRU W-102. PLEASE SELECT
 SYSTEM NO. USED. ALL APPLICABLE DETAILS AND ATTACHMENTS
 MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL
 DRAWINGS. DETAILS AND ATTACHMENTS NOT SPECIFICALLY
 COVERED IN PRODUCT APPROVALS WILL NEED SITE-SPECIFIC
 ENGINEERING. PROJECT IS IN EXPOSURE CATEGORY C; SYSTEM
 CHOSEN MUST MEET OR EXCEED ZONE 3 MINIMUM DESIGN
 PRESSURE REQUIREMENT 0F -108.17 OR PROVIDE SIGNED AND
 SEALED NAILING CALCULATIONS FOR ZONE 3 IF REPAIR IS
 REROOF. IF REPAIR IS A RECOVER PROVIDE DOCUMENTS TO
 DEMONSTRATE COMPLIANCE WITH 1511.3 OF THE 2020 FBC
 BUILDING & LIMITATION #5.6.1 OR 5.6.2 OF PRODUCT
 APPROVAL FL2533 R-24. SECOND REQUEST.
  