Date |
Text |
2021-06-11 17:13:31 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT-21050062 |
| 6/11/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE |
| 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN |
| CAPS. |
| |
| 3) FAILED. A5: PROVIDE ENLARGED SHOWER COMPARTMENT |
| ACCESSIBILITY DETAILS: |
| A) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF |
| GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| 608.3.1. 18-INCH GRAB BAR LENGTH NOT SHOWN- REFER TO |
| FIGURE 608.3.1. |
| B) FAILED. TYPE OF SEAT, SEAT LOCATION, AND DIMENSIONS- |
| SECTIONS 608.4. 610.3, 610.3.1, & 610.3.2. REFER TO |
| FIGURES 610.3.1 AND 610.3.2 AND SHOW COMPLIANCE FOR |
| SEAT DIMENSIONS AND EDGE CLEARANCES. |
| C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER |
| SPRAY IN THE SHOWER- SECTION 608.5.1. THE CONTROLS |
| SHALL BE LOCATED ON THE SIDE WALL OPPOSITE OF THE SEAT. |
| PLEASE SEE FIGURE 608.5.1 AND PROVIDE A LOCATION |
| DIAGRAM THAT MEETS COMPLIANCE. PLEASE ADD THE SHOWER |
| CONTROL, FAUCET, AND SPRAY TO THE FIXTURE SCHEDULE ON |
| SHEET P4.0. |
| |
| 5) FAILED. A5: PROVIDE A SHOWER PAN AND CURB DETAIL IN |
| COMPLIANCE WITH- SECTION 608.7 FBC ACC & SECTION |
| 421.5.2 FBC P. THE DETAIL INDICATES A 3/8-INCH PER FT. |
| SLOPE. THE MAXIMUM ALLOWABLE SLOPE IS 1/4-INCH PER FT.- |
| SECTION 421.5.1.2. |
| |
| 6) FAILED. A3.0 & A5: PLEASE PROVIDE DETAILS SHOWING |
| THE DIMENSIONS OF THE WALL TILE SURROUND FOR THE |
| BATHROOM FIXTURES AND THE MOP SINK- SECTION 310.3 FBC P |
| AND SECTION 1210.2.2 FBC B. NO CORRECTIONS OR WALL TILE |
| CALLED OUT FOR BATHROOMS. |
| |
| NEW COMMENT. |
| 1) SHEET A1: PLEASE SHOW THE CLEAR FLOOR SPACE FORWARD |
| APPROACH DIAGRAMS AND DIMENSIONS AT THE ACCESSIBLE |
| SINKS. PLEASE NOTE SECTION 212.3 SINKS FBC ACC: |
| WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO |
| FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH |
| ACCESSIBLE ROOM OR SPACE SHALL COMPLY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |