Plan Review Notes
Plan Review Notes For Permit 21050062
Permit Number 21050062
Review Stop P
Sequence Number 2
Notes
Date Text
2021-06-11 17:13:312ND REVIEW FBC-2020 PLUMBING
 PERMIT-21050062
 6/11/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES IN
 CAPS.
  
 3) FAILED. A5: PROVIDE ENLARGED SHOWER COMPARTMENT
 ACCESSIBILITY DETAILS:
 A) FAILED. LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.1. 18-INCH GRAB BAR LENGTH NOT SHOWN- REFER TO
 FIGURE 608.3.1.
 B) FAILED. TYPE OF SEAT, SEAT LOCATION, AND DIMENSIONS-
 SECTIONS 608.4. 610.3, 610.3.1, & 610.3.2. REFER TO
 FIGURES 610.3.1 AND 610.3.2 AND SHOW COMPLIANCE FOR
 SEAT DIMENSIONS AND EDGE CLEARANCES.
 C) FAILED. LOCATION OF CONTROL, FAUCET, AND SHOWER
 SPRAY IN THE SHOWER- SECTION 608.5.1. THE CONTROLS
 SHALL BE LOCATED ON THE SIDE WALL OPPOSITE OF THE SEAT.
 PLEASE SEE FIGURE 608.5.1 AND PROVIDE A LOCATION
 DIAGRAM THAT MEETS COMPLIANCE. PLEASE ADD THE SHOWER
 CONTROL, FAUCET, AND SPRAY TO THE FIXTURE SCHEDULE ON
 SHEET P4.0.
  
 5) FAILED. A5: PROVIDE A SHOWER PAN AND CURB DETAIL IN
 COMPLIANCE WITH- SECTION 608.7 FBC ACC & SECTION
 421.5.2 FBC P. THE DETAIL INDICATES A 3/8-INCH PER FT.
 SLOPE. THE MAXIMUM ALLOWABLE SLOPE IS 1/4-INCH PER FT.-
 SECTION 421.5.1.2.
  
 6) FAILED. A3.0 & A5: PLEASE PROVIDE DETAILS SHOWING
 THE DIMENSIONS OF THE WALL TILE SURROUND FOR THE
 BATHROOM FIXTURES AND THE MOP SINK- SECTION 310.3 FBC P
 AND SECTION 1210.2.2 FBC B. NO CORRECTIONS OR WALL TILE
 CALLED OUT FOR BATHROOMS.
  
 NEW COMMENT.
 1) SHEET A1: PLEASE SHOW THE CLEAR FLOOR SPACE FORWARD
 APPROACH DIAGRAMS AND DIMENSIONS AT THE ACCESSIBLE
 SINKS. PLEASE NOTE SECTION 212.3 SINKS FBC ACC:
 WHERE SINKS ARE PROVIDED, AT LEAST 5 PERCENT, BUT NO
 FEWER THAN ONE, OF EACH TYPE PROVIDED IN EACH
 ACCESSIBLE ROOM OR SPACE SHALL COMPLY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  