2021-05-18 13:30:081ST REVIEW FBC-2020 PLUMBING
 PERMIT-21050062
 5/18/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET T1.0: THE DRINKING FOUNTAIN IS A REQUIRED
 FIXTURE FOR BUSINESS OCCUPANCIES AND THE SPECIFIED
 ELECTRIC WATER COOLER SPECIFIED CAN BE SUBSTITUTED FOR
 NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER OF
 DRINKING FOUNTAINS- SECTION 410.4 FBC P. REFER TO
 SECTION 211.2 FBC ACC MINIMUM NUMBER. NO FEWER THAN TWO
 DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING
 FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6
 (WHEELCHAIR ACCESSIBLE) AND ONE DRINKING FOUNTAIN SHALL
 COMPLY WITH 602.7 (STANDING PERSONS). EXCEPTION: WHERE
 A SINGLE DRINKING FOUNTAIN COMPLIES WITH 602.1 THROUGH
 602.6 AND 602.7, IT SHALL BE PERMITTED TO BE
 SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS. PLEASE
 REVISE THE PLANS ACCORDINGLY TO SHOW:
 A) LOCATION OF THE HI LO DRINKING.
 B) PLUMBING PIPING REQUIREMENTS.
 C) ACCESSIBILITY COMPLIANCES- REFER TO SECTIONS 306,
 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN
 INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE
 AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS.
 SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A
 FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION
 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE
 FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2
 PROTRUSION LIMITS.
  
 2) SHEET A1 & A5: MISSING AND INCORRECT ACCESSIBILITY
 DETAILS- FBC ACC. PLEASE NOTE THAT THE OWNER'S PRIVATE
 BATHROOM IS ALSO LABELED AS A STAFF BATHROOM. THE
 EXCEPTIONS LISTED FOR BATHROOMS AND FIXTURES IN THE FBC
 ACC APPLY TO BATHROOMS ACCESSED ONLY THROUGH A PRIVATE
 OFFICE. FULL COMPLIANCE WITH THE FBC ACC IS REQUIRED.
 PLEASE PROVIDE:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSET, LAVATORY, AND SHOWER- SECTIONS 604.3.1,
 606.2, 608.2. PLEASE INCLUDE THE DIMENSIONS OF THE
 SHOWER- 608.2.1.
 B) TURNING SPACE DIAGRAM AND DIMENSIONS- SECTION 304.3.
 C) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACES
 FOR THE SHOWER UNLESS MEETING EITHER EXCEPTION 1 OR 2
 UNDER SECTION 603.2.3.
 D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL-
 SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR - SECTION 604.4.
 F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION
 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION
 606.2.
  
 3) A5: PROVIDE ENLARGED SHOWER COMPARTMENT
 ACCESSIBILITY DETAILS:
 A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND
 608.3.1
 B) TYPE OF SEAT, SEAT LOCATION, AND DIMENSIONS-
 SECTIONS 608.4. 610.3, 610.3.1, & 610.3.2
 C) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SECTION 608.5.1.
  
 4) A1 & A5: THE DOORS IN THE UNISEX TOILET ROOMS SHALL
 NOT SWING INTO THE CLEAR FLOOR SPACES FOR THE
 LAVATORIES UNLESS MEETING EITHER EXCEPTION 1 OR 2 UNDER
 SECTION 603.2.3.
  
 5) A5: PROVIDE A SHOWER PAN AND CURB DETAIL IN
 COMPLIANCE WITH- SECTION 608.7 FBC ACC & SECTION
 421.5.2 FBC P.
  
 6) A3.0 & A5: PLEASE PROVIDE DETAILS SHOWING THE
 DIMENSIONS OF THE WALL TILE SURROUND FOR THE BATHROOM
 FIXTURES AND THE MOP SINK- SECTION 310.3 FBC P AND
 SECTION 1210.2.2 FBC B.
  
 7) P1, P3, & P4: THE MIB1HAAB IS NOT A WASHER BOX.
 PLEASE IDENTIFY THE DEVICE CORRECTLY AND INDICATE WHAT
 FIXTURE OR APPLIANCE IT IS SERVING- SECTION 107.2.1
 WPB. PLEASE NOTE THAT A BACKFLOW PREVENTER IS REQUIRED
 FOR WATER SUPPLY LINES TO ICE MAKERS, COFFEE MACHINES
 ETC. SECTION 608.3 FBC P.
  
 8) D1: SHOW AREAS OF SLAB DEMOLITION AND PROVIDE A SLAB
 REPAIR DETAIL- SECTION 107.2.1 WPB.
  
 9) P4: PROVIDE THE EFFICIENCY RATING OF THE WATER
 HEATER- TABLE C404.2 FBC EC.
  
 10) P4: PLEASE PROVIDE A TMV INSTALLATION DETAIL AT THE
 SINKS- SECTION 607.2.1 FBC P.
  
 11) PROVIDE A CIVIL PLAN SHOWING THE LOCATIONS OF THE
 NEW WATER SERVICE LINE, POINT OF CONNECTION TO THE
 WATER MAIN, WATER METER, AND BACKFLOW PREVENTER-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT A FL. LICENSED
 PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR
 INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE
 WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF
 ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY
 THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION
 BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB
 UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR
 FURTHER INFORMATION.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  