2021-05-18 13:30:08 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT-21050062 |
| 5/18/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET T1.0: THE DRINKING FOUNTAIN IS A REQUIRED |
| FIXTURE FOR BUSINESS OCCUPANCIES AND THE SPECIFIED |
| ELECTRIC WATER COOLER SPECIFIED CAN BE SUBSTITUTED FOR |
| NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER OF |
| DRINKING FOUNTAINS- SECTION 410.4 FBC P. REFER TO |
| SECTION 211.2 FBC ACC MINIMUM NUMBER. NO FEWER THAN TWO |
| DRINKING FOUNTAINS SHALL BE PROVIDED. ONE DRINKING |
| FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH 602.6 |
| (WHEELCHAIR ACCESSIBLE) AND ONE DRINKING FOUNTAIN SHALL |
| COMPLY WITH 602.7 (STANDING PERSONS). EXCEPTION: WHERE |
| A SINGLE DRINKING FOUNTAIN COMPLIES WITH 602.1 THROUGH |
| 602.6 AND 602.7, IT SHALL BE PERMITTED TO BE |
| SUBSTITUTED FOR TWO SEPARATE DRINKING FOUNTAINS. PLEASE |
| REVISE THE PLANS ACCORDINGLY TO SHOW: |
| A) LOCATION OF THE HI LO DRINKING. |
| B) PLUMBING PIPING REQUIREMENTS. |
| C) ACCESSIBILITY COMPLIANCES- REFER TO SECTIONS 306, |
| 307, AND 602 FBC ACC AND PROVIDE DRINKING FOUNTAIN |
| INSTALLATION DETAILS AND ELEVATION VIEWS SHOWING KNEE |
| AND TOE CLEARANCES, SPOUT HEIGHTS, AND SPOUT LOCATIONS. |
| SHOW THE REQUIRED 30 X 48 IN. CLEAR FLOOR SPACE FOR A |
| FORWARD WHEELCHAIR APPROACH TO THE FOUNTAIN- SECTION |
| 602.2 FBC ACC, AND SHOW HOW THE LOCATIONS OF THE |
| FOUNTAINS WILL BE IN COMPLIANCE WITH SECTION 307.2 |
| PROTRUSION LIMITS. |
| |
| 2) SHEET A1 & A5: MISSING AND INCORRECT ACCESSIBILITY |
| DETAILS- FBC ACC. PLEASE NOTE THAT THE OWNER'S PRIVATE |
| BATHROOM IS ALSO LABELED AS A STAFF BATHROOM. THE |
| EXCEPTIONS LISTED FOR BATHROOMS AND FIXTURES IN THE FBC |
| ACC APPLY TO BATHROOMS ACCESSED ONLY THROUGH A PRIVATE |
| OFFICE. FULL COMPLIANCE WITH THE FBC ACC IS REQUIRED. |
| PLEASE PROVIDE: |
| A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE |
| WATER CLOSET, LAVATORY, AND SHOWER- SECTIONS 604.3.1, |
| 606.2, 608.2. PLEASE INCLUDE THE DIMENSIONS OF THE |
| SHOWER- 608.2.1. |
| B) TURNING SPACE DIAGRAM AND DIMENSIONS- SECTION 304.3. |
| C) DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACES |
| FOR THE SHOWER UNLESS MEETING EITHER EXCEPTION 1 OR 2 |
| UNDER SECTION 603.2.3. |
| D) CENTERLINE OF THE WATER CLOSET FROM THE SIDE WALL- |
| SECTION 604.2. |
| E) HEIGHTS OF THE WATER CLOSET SEAT FROM THE FINISHED |
| FLOOR - SECTION 604.4. |
| F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE |
| FROM THE FINISHED FLOOR- SECTION 606.3. |
| G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOORS TO |
| THE REFLECTIVE SURFACES- SECTION 603.3 |
| H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, |
| FIGURES 604. |
| I) LOCATION OF THE WATER CLOSET FLUSH CONTROL - SECTION |
| 604.6. |
| J) CENTERLINE OF THE TOILET PAPER DISPENSER MEASURED |
| FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND |
| FIGURE 604.7. |
| K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SECTION |
| 606.2. |
| |
| 3) A5: PROVIDE ENLARGED SHOWER COMPARTMENT |
| ACCESSIBILITY DETAILS: |
| A) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB |
| BARS FOR THE ACCESSIBLE SHOWER- SECTION 608.3 AND |
| 608.3.1 |
| B) TYPE OF SEAT, SEAT LOCATION, AND DIMENSIONS- |
| SECTIONS 608.4. 610.3, 610.3.1, & 610.3.2 |
| C) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE |
| SHOWER- SECTION 608.5.1. |
| |
| 4) A1 & A5: THE DOORS IN THE UNISEX TOILET ROOMS SHALL |
| NOT SWING INTO THE CLEAR FLOOR SPACES FOR THE |
| LAVATORIES UNLESS MEETING EITHER EXCEPTION 1 OR 2 UNDER |
| SECTION 603.2.3. |
| |
| 5) A5: PROVIDE A SHOWER PAN AND CURB DETAIL IN |
| COMPLIANCE WITH- SECTION 608.7 FBC ACC & SECTION |
| 421.5.2 FBC P. |
| |
| 6) A3.0 & A5: PLEASE PROVIDE DETAILS SHOWING THE |
| DIMENSIONS OF THE WALL TILE SURROUND FOR THE BATHROOM |
| FIXTURES AND THE MOP SINK- SECTION 310.3 FBC P AND |
| SECTION 1210.2.2 FBC B. |
| |
| 7) P1, P3, & P4: THE MIB1HAAB IS NOT A WASHER BOX. |
| PLEASE IDENTIFY THE DEVICE CORRECTLY AND INDICATE WHAT |
| FIXTURE OR APPLIANCE IT IS SERVING- SECTION 107.2.1 |
| WPB. PLEASE NOTE THAT A BACKFLOW PREVENTER IS REQUIRED |
| FOR WATER SUPPLY LINES TO ICE MAKERS, COFFEE MACHINES |
| ETC. SECTION 608.3 FBC P. |
| |
| 8) D1: SHOW AREAS OF SLAB DEMOLITION AND PROVIDE A SLAB |
| REPAIR DETAIL- SECTION 107.2.1 WPB. |
| |
| 9) P4: PROVIDE THE EFFICIENCY RATING OF THE WATER |
| HEATER- TABLE C404.2 FBC EC. |
| |
| 10) P4: PLEASE PROVIDE A TMV INSTALLATION DETAIL AT THE |
| SINKS- SECTION 607.2.1 FBC P. |
| |
| 11) PROVIDE A CIVIL PLAN SHOWING THE LOCATIONS OF THE |
| NEW WATER SERVICE LINE, POINT OF CONNECTION TO THE |
| WATER MAIN, WATER METER, AND BACKFLOW PREVENTER- |
| SECTION 107.2.1 WPB. PLEASE NOTE THAT A FL. LICENSED |
| PLUMBING CONTRACTOR SHALL OBTAIN A SEPARATE PERMIT FOR |
| INSTALLATION OF THE BACKFLOW PREVENTER IN ACCORDANCE |
| WITH SECTION 105.1 WPB AND SEC. 90-33 WPB CODE OF |
| ORDINANCES. THE DEVICE SHALL BE TESTED AND CERTIFIED BY |
| THE WPB UTILITIES DEPARTMENT PRIOR TO FINAL INSPECTION |
| BY THE BUILDING DEPARTMENT. PLEASE CONTACT THE WPB |
| UTILITIES CENTRAL OPERATIONS DEPT.AT 561-822-2210 FOR |
| FURTHER INFORMATION. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |