2021-05-26 13:14:08OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE WALL FINISH AROUND THE MOP SINK TO
 COMPLY WITH FBC 1210.2.2 (DRYWALL IS NOT CONSIDERED A
 HARD SURFACE)
 2) PLEASE SHOW THE ATTACHMENTS FOR THE WATER HEATER
 SHELF TO THE WALL.
 3) PLEASE SHOW THE EXTERIOR SIDING ATTACHMENTS TO THE
 EXTERIOR WALL - EXTERIOR SIDING IS SUBJECT TO WIND
 LOADS - FBC 1609
 4) PLEASE SHOW THE WIND DESIGN DATA USED PER FBC
 1603.1.4
 5) SHOWER PROVIDED NEEDS TO BE ACCESSIBLE PER FBC
 213.3.6 (PLEASE SHOW ALL ACCESSIBLE DETAILS)
 6) PLEASE SHOW INTERIOR GLASS WALL PANELS TO COMPLY
 WITH SAFETY GLAZING REQUIREMENTS FBC 2406.1
 7) DRAWINGS NEED TO BE SIGNED AND SEALED BY THE
 DESIGNER FBC 107.1
 8) PLEASE PROVIDE COMPLETE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE NEW EXTERIOR WINDOWS AND
 DOORS. ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 MARKED APPROVED BY THE DESIGNER OF RECORD OR BE LISTED
 BY THE PRODUCT APPROVAL NUMBER ON THE DRAWINGS. FBC
 107.3.4
 9) PLEASE SHOW SHOWER WALL FINISH TO COMPLY WITH FBC
 1210.2.3
  
  