Date Text
2021-05-24 14:06:22RESPONSE TO DANIEL BARRETT EMAIL DRY FLOODPROOFING
 PROPOSAL:
  
 GOOD AFTERNOON LADIES AND GENTLEMAN,
 ARCHITECT IS PROPOSING DRY FLOODPROOFING. DRY
 FLOODPROOFING IS NOT ALLOWED IN RESIDENTIAL STRUCTURES.
 ASCE 24-14 SEC. 6.2.1 .
  
 ACCORDING TO ASCE 24-14 SEC. 1.5.2 THE TRASH ROOM SHALL
 HAVE THE LOWEST FLOOR ELEVATED TO OR ABOVE THE DESIGN
 FLOOD ELEVATION (DFE).
  
 ONLY ENCLOSED AREAS THAT ARE USED SOLELY FOR PARKING OF
 VEHICLES, BUILDING ACCESS, OR STORAGE SHALL BE ALLOWED
 BELOW THE DFE.
 TRASH ROOM IS NONE OF THE ABOVE.
  
 I HOPE THIS HELPS.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
 FINAL ELEVATION CERTIFICATE, THIRD REVIEW COMMENTS:
 SUBMITTAL #21041684
  
 (NOTE: NUMBERING OF COMMENTS WAS REVISED TO SIMPLIFY
 REVIEW. ORIGINAL COMMENT IS THE SAME FROM PREVIOUS
 REVIEW).
  
 ORIGINAL COMMENT:
 1- REVISED FINAL SURVEY SHOWS 14.24 (NAVD) FINISH FLOOR
 ELEVATION AT TRASH ROOM. THIS ELEVATION IS BELOW THE
 DESIGN FLOOD ELEVATION OF 14.7 (NAVD) SPECIFIED BY THE
 DESIGNER OF RECORD. SEE SHEET A-2.1 FOR PROPOSED
 ELEVATION (16.25 NGVD). COORDINATE WITH THE DESIGNER OF
 RECORD AND SHOW COMPLIANCE WITH THE REQUIRED FINISH
 ELEVATION.
 SEC. 1612.4 FBC-BUILDING. SEC. 1.5.2 ASCE 24.
 NOTE: SEE REVISION #19110684.
  
 RESPONSE:
 RESPONSE LETTER FROM HUMBERTO BRICENO STATES "THE
 ELEVATION 14.24' WAS TAKEN AT THE THRESHOLD, THE
 MEASURED FINISH FLOOR ELEVATION IS 14.31' NAVD88
 (15.83' NGVD29) WHICH IS THE DESIGN ELEVATION."
  
 THIS COMMENTS APPLY TO HUMBERTO BRICENO'S RESPONSE
 LETTER:
 (A) THE DESIGN FLOOD ELEVATION SHOWN ON PLANS IS 16.25'
 NGVD. THEREFORE, 15.83' NGVD29 IS NOT THE DESIGN
 ELEVATION. HUMBERTO'S RESPONSE IS INCORRECT.
  
 (B)TRASH ROOM FINISH FLOOR ELEVATION IS BELOW THE
 REQUIRED DESIGN FLOOD ELEVATION. FINISH FLOOR NEEDS TO
 BE RAISED TO MEET THE 16.25' NGVD SPECIFIED BY THE
 ARCHITECT OF RECORD.
 IF THERE ARE ANY CHANGES TO THE APPROVED PLANS, THEN
 THEY NEED TO BE ADDRESSED BY THE ARCHITECT OF RECORD BY
 REVISING PLANS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH SEC. 1612.4 FBC-BUILDING.
  
 (C)BASED ON HUMBERTO'S RESPONSE LETTER AND CONVERSATION
 WITH LUIS ORTIZ (SURVEYOR), THE TRASH ROOM HAS AN
 SLOPED FLOOR. IF THE FLOOR IS SLOPED, THEN THE FINISH
 FLOOR ELEVATION OF 15.83' NGVD29 IS INCORRECT BECAUSE
 THERE ARE LOW AND HIGH ELEVATIONS ON THE SAME ROOM.
 SPOT FINISH FLOOR ELEVATIONS SHOULD BE GIVEN AS DONE
 WITH THE LOADING AREA. THIS IS IMPORTANT BECAUSE THIS
 ROOM HAS EQUIPMENT THAT NEEDS TO BE LOCATED AT THE
 DESIGN FLOOD ELEVATION. REVISE AS REQUIRED AND CLEARLY
 PROVIDE THE FINISH FLOOR ELEVATION SPOT ELEVATION WHERE
 THE TRASH ROOM EQUIPMENT IS LOCATED.
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
  
 ORIGINAL COMMENT:
 2- CLARIFY WHY DOMESTIC PUMP ROOM SAYS F.F.E.=14.71
 SINCE THERE IS AN SPOT ELEVATION OF 14.61 SHOWN AT THE
 ENTRY OF THIS ROOM.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE WITH RESPONSE (C) TO ITEM #1 ABOVE. SIMILAR
 SITUATION WITH SLOPED FLOOR.
  
  
 ORIGINAL COMMENT:
 3- BASED ON THE REVISED FINAL SURVEY IT LOOKS LIKE THE
 LOWEST ELEVATION OF MACHINERY/EQUIPMENT IS NOT THE
 GENERATOR PAD. THE EQUIPMENT LOCATED IN THE ROOMS
 ADJACENT TO THE LOADING AREA SEEM TO BE LOWER THAN THE
 GENERATOR PAD. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 THIS ITEM WAS REVISED, BUT THIS WILL NEED TO BE REVISED
 AGAIN ONCE ITEM #1 IS ADDRESSED AND IN COMPLIANCE.
 NOTE: REVISE COMMENT C2(E) AT THE BOTTOM OF SECTION D.
 NEED TO IDENTIFY THE EQUIPMENT. "TRASH ROOM" IS NOT AN
 EQUIPMENT.
  
 ORIGINAL COMMENT:
 4- PROVIDE PHOTOS SHOWING THE VENTS SPECIFIED ON ITEM
 A9(B).
 NOTE: COORDINATE WITH VENTS SHOWN ON SHEET A.2.1 AND
 DETAILS 4 AND 8 ON SHEET A-8.1.1. THERE IS A VENT
 INSIDE THE GARAGE CONNECTING TO THE OUTSIDE WALL. THE
 OTHER VENT CONSIDERED BY THE ARCHITECT OF RECORD IS THE
 ENTRANCE TO THE GARAGE. SHOW ALL VENTS. SEE ITEM A6
 FEMA ELEVATION CERTIFICATE INSTRUCTIONS.
 ALSO, ALL PHOTOS NEED TO BE AT LEAST 3"X3". REVISE
 PHOTO THREE ON PAGE 6 OF 6.
  
 SEE ARCHITECT'S REVISION #8 ON PLANS AND REVISION
 #19110684 CITY RECORDS.
  
 RESPONSE:
 (A)VENTS SHOWN ON THE PHOTOS ON PAGE 7 DON'T MATCH THE
 ONES DESIGNED BY THE DESIGNER OF RECORD. SEE SHEET
 SHEET A.2.1 AND DETAILS 4 AND 8 ON SHEET A-8.1.1.
 NEED TO INSTALL VENTS AS SPECIFIED BY THE ARCHITECT OF
 RECORD.
 IF THERE ARE ANY CHANGES TO THE APPROVED PLANS, THEN
 THEY NEED TO BE ADDRESSED BY THE ARCHITECT OF RECORD BY
 REVISING PLANS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH SEC. 1612.4 FBC-BUILDING.
 NOTE:THERE ARE SPECIFIC REQUIREMENTS FOR NON-ENGINEERED
 VENTS. SEE SEC. 2.7.2.1 ASCE 24.
  
 (B)BASED ON PHOTO #5 SHOWN ON PAGE 7, IT LOOKS LIKE THE
 PASSAGE FROM THE GARAGE INTERIOR VENT TO THE OUTSIDE
 VENT DOESN'T COMPLY WITH THE ARCHITECT'S DESIGN.
 APPROVED REVISION #19110684 SHOWS DETAIL A ON SHEET
 A-2.1 WITH A VOID SPACE BETWEEN THE INTERIOR AND
 EXTERIOR VENTS. THIS DETAIL SHOWS THIS VOID WITH A
 CONCRETE SLAB AS THE FINISH FLOOR. PHOTO #5 SEEMS TO
 SHOW DIRT INSTEAD OF CONCRETE SLAB.
 THIS NEEDS TO BE ADDRESSED.
 IF THERE ARE ANY CHANGES TO THE APPROVED PLANS, THEN
 THEY NEED TO BE ADDRESSED BY THE ARCHITECT OF RECORD BY
 REVISING PLANS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH SEC. 1612.4 FBC-BUILDING.
  
 (C)PHOTO #5 SHOWN ON PAGE 7 LOOKS LIKE IT WAS TAKEN
 WHEN THE BUILDING WAS UNDER CONSTRUCTION. THIS IS A
 FINAL ELEVATION CERTIFICATE. PHOTO NEEDS TO BE TAKEN
 WHEN CONSTRUCTION IS COMPLETE, INCLUDING THE FINAL
 GRADING.
  
 (D) ALL PHOTOS ON PAGE 7 AND 8 NEED THE DATE WHEN THEY
 ARE TAKEN.
 THEY NEED TO BE TAKEN WITHIN 90 DAYS FROM DATE OF
 CERTIFICATION. SEE ITEM A6 OF FEMA ELEVATION
 CERTIFICATE INSTRUCTIONS.
  
 ORIGINAL COMMENT:
 5- ITEM A9(C) WAS REVISED. THIS ITEM IS FOR THE NET
 AREA OF FLOOD OPENINGS. AREA SHOWN IS WAY TOO HIGH
 COMPARED TO THE ONE SPECIFIED BY THE ARCHITECT OF
 RECORD ON SHEET SHEET A.2.1 AND DETAILS 4 AND 8 ON
 SHEET A-8.1.1. PLEASE COORDINATE WITH ARCHITECT AND
 REVISE AS REQUIRED. ONLY THE AREA BELOW THE DESIGN
 FLOOD ELEVATION COUNTS. ALSO, NEED TO SPECIFY THE
 ACTUAL NET AREA (EXCLUDING VENT FRAME)OF THE INSTALLED
 VENTS.
  
 RESPONSE:
 BASED ON THE REVISED NET AREA, IT LOOKS LIKE THE NET
 AREA DOESN'T COMPLY WITH THE NET AREA SPECIFIED BY THE
 ARCHITECT OF RECORD ON FLOOD VENT CALCULATIONS ON SHEET
 A-2.1.
 THIS NEEDS TO BE ADDRESSED. COORDINATE WITH ITEM #4
 ABOVE.
 IF THERE ARE ANY CHANGES TO THE APPROVED PLANS, THEN
 THEY NEED TO BE ADDRESSED BY THE ARCHITECT OF RECORD BY
 REVISING PLANS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH SEC. 1612.4 FBC-BUILDING.
  
 NEW COMMENTS:
 6- I APOLOGIZE FOR THIS NEW COMMENT, BUT AFTER
 REVIEWING SHEET A-2.1
 TO REVIEW ARCHITECT'S ORIGINAL VENTS DESIGN, I REALIZED
 THE SURVEY SHOW SOME PARTITIONS ON THE NORTH SIDE OF
 THE GARAGE. THESE PARTITIONS ARE NOT SHOWN ON THE
 ARCHITECT'S PLANS. THESE PARTITIONS SEEM TO BE BLOCKING
 THE FLOOD VENTS. THIS NEEDS TO BE ADDRESSED.
 IF THERE ARE ANY CHANGES TO THE APPROVED PLANS, THEN
 THEY NEED TO BE ADDRESSED BY THE ARCHITECT OF RECORD BY
 REVISING PLANS AND SPECIFICATIONS SHOWING COMPLIANCE
 WITH SEC. 1612.4 FBC-BUILDING.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  