2021-05-14 19:46:51 | FINAL ELEVATION CERTIFICATE, SECOND REVIEW COMMENTS: |
| SUBMITTAL #21041684 |
| |
| ORIGINAL COMMENT: |
| 1- REVISE INFORMATION ENTERED IN SECTION C2: |
| (A) THERE IS NO INFORMATION IN THE SURVEY FOR THE |
| ELEVATION AT THE LOADING AREA ON THE NORTH SIDE OF THE |
| BUILDING. ACCORDING TO PLANS, THE ELEVATION AT THE |
| ENTRANCE OF THE LOADING AREA IS LOWER THAN THE REST OF |
| THE FLOOR. THIS LOOKS LIKE THE TOP OF BOTTOM FLOOR. |
| REVISE AS REQUIRED. |
| PROVIDE FINAL SURVEY SHOWING ELEVATIONS IN THE LOADING |
| AREA. (INCLUDE THE FIRE PUMP ROOM, TRASH ROOM, DOMESTIC |
| PUMP ROOM). |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| RESPONSE: |
| (1)REVISED FINAL SURVEY SHOWS 14.24 (NAVD) FINISH FLOOR |
| ELEVATION AT TRASH ROOM. THIS ELEVATION IS BELOW THE |
| DESIGN FLOOD ELEVATION OF 14.7 (NAVD) SPECIFIED BY THE |
| DESIGNER OF RECORD. SEE SHEET A-2.1 FOR PROPOSED |
| ELEVATION (16.25 NGVD). COORDINATE WITH THE DESIGNER OF |
| RECORD AND SHOW COMPLIANCE WITH THE REQUIRED FINISH |
| ELEVATION. |
| SEC. 1612.4 FBC-BUILDING. SEC. 1.5.2 ASCE 24. |
| |
| (2)CLARIFY WHY DOMESTIC PUMP ROOM SAYS F.F.E.=14.71 |
| SINCE THERE IS AN SPOT ELEVATION OF 14.61 SHOWN AT THE |
| ENTRY OF THIS ROOM. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| (3)CLARIFY WHY LOADING AREA F.F.E.=14.12 AND THERE IS |
| AN SPOT ELEVATION OF 14.62 SHOWN AT THE ENTRANCE OF THE |
| LOADING AREA. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| (B)OK. |
| (C)OK. |
| |
| ORIGINAL COMMENT: |
| (D)ACCORDING TO FINAL SURVEY SUBMITTED IT LOOKS LIKE |
| THE TOP OF ATTACHED GARAGE ELEVATION IS TAKEN AT A |
| MIDPOINT OF THE GARAGE RAMP. THE LOWEST ELEVATION OF |
| THE GARAGE IS AT THE ENTRANCE OF THE GARAGE. REVISE AS |
| REQUIRED. |
| |
| RESPONSE: |
| GARAGE ELEVATION WAS CHANGED, BUT THE LOCATION WHERE |
| THIS ELEVATION IS SHOWN IS MISLEADING. THIS ELEVATION |
| IS SHOWN AT MID POINT OF THE GARAGE. THIS GARAGE HAS |
| DIFFERENT LEVELS AND THE POINT WHERE THE REVISED |
| ELEVATION IS SHOWN IS HIGHER THAN THE NUMBER SHOWN. |
| TYPICALLY, THE ELEVATIONS ARE MARKED AT THE POINT WHERE |
| THE ELEVATION IS TAKEN. REVISE AS REQUIRED TO AVOID |
| CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| NEW COMMENT TO THIS ITEM: |
| (E)BASED ON THE REVISED FINAL SURVEY IT LOOKS LIKE THE |
| LOWEST ELEVATION OF MACHINERY/EQUIPMENT IS NOT THE |
| GENERATOR PAD. THE EQUIPMENT LOCATED IN THE ROOMS |
| ADJACENT TO THE LOADING AREA SEEM TO BE LOWER THAN THE |
| GENERATOR PAD. REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| (F)OK. |
| (G)OK. |
| (H)OK. |
| |
| ORIGINAL COMMENT: |
| 2- PROVIDE PHOTOS SHOWING THE VENTS SPECIFIED ON ITEM |
| A9(B). |
| NOTE: COORDINATE WITH VENTS SHOWN ON SHEET A.2.1 AND |
| DETAILS 4 AND 8 ON SHEET A-8.1.1. THERE IS A VENT |
| INSIDE THE GARAGE CONNECTING TO THE OUTSIDE WALL. THE |
| OTHER VENT CONSIDERED BY THE ARCHITECT OF RECORD IS THE |
| ENTRANCE TO THE GARAGE. SHOW ALL VENTS. SEE ITEM A6 |
| FEMA ELEVATION CERTIFICATE INSTRUCTIONS. |
| ALSO, ALL PHOTOS NEED TO BE AT LEAST 3"X3". REVISE |
| PHOTO THREE ON PAGE 6 OF 6. |
| |
| SEE ARCHITECT'S REVISION #8 ON PLANS AND REVISION |
| #19110684 CITY RECORDS. |
| |
| RESPONSE: |
| (1)ONLY THE INSIDE VENT WAS SHOWN. NEED PHOTO SHOWING |
| THE OUTSIDE VENT THAT CONNECTS TO THE INSIDE VENT. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| (2)VENT SHOWN ON THE PHOTO DOESN'T SEEM TO MATCH THE |
| ONE DESIGNED BY THE DESIGNER OF RECORD. SEE SHEET SHEET |
| A.2.1 AND DETAILS 4 AND 8 ON SHEET A-8.1.1. DESIGNER OF |
| RECORD NEEDS TO REVISE VENT DESIGN OR CONTRACTOR NEEDS |
| TO INSTALL VENT THAT MATCHES THE ONE DESIGNED BY THE |
| ARCHITECT OF RECORD. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| |
| 3- OK. |
| |
| NEW COMMENT: |
| 4- ITEM A9(C) WAS REVISED. THIS ITEM IS FOR THE NET |
| AREA OF FLOOD OPENINGS. AREA SHOWN IS WAY TOO HIGH |
| COMPARED TO THE ONE SPECIFIED BY THE ARCHITECT OF |
| RECORD ON SHEET SHEET A.2.1 AND DETAILS 4 AND 8 ON |
| SHEET A-8.1.1. PLEASE COORDINATE WITH ARCHITECT AND |
| REVISE AS REQUIRED. ONLY THE AREA BELOW THE DESIGN |
| FLOOD ELEVATION COUNTS. ALSO, NEED TO SPECIFY THE |
| ACTUAL NET AREA (EXCLUDING VENT FRAME)OF THE INSTALLED |
| VENTS. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |
| |
| |
| |
| *********************** |