2021-05-14 19:46:51FINAL ELEVATION CERTIFICATE, SECOND REVIEW COMMENTS:
 SUBMITTAL #21041684
  
 ORIGINAL COMMENT:
 1- REVISE INFORMATION ENTERED IN SECTION C2:
 (A) THERE IS NO INFORMATION IN THE SURVEY FOR THE
 ELEVATION AT THE LOADING AREA ON THE NORTH SIDE OF THE
 BUILDING. ACCORDING TO PLANS, THE ELEVATION AT THE
 ENTRANCE OF THE LOADING AREA IS LOWER THAN THE REST OF
 THE FLOOR. THIS LOOKS LIKE THE TOP OF BOTTOM FLOOR.
 REVISE AS REQUIRED.
 PROVIDE FINAL SURVEY SHOWING ELEVATIONS IN THE LOADING
 AREA. (INCLUDE THE FIRE PUMP ROOM, TRASH ROOM, DOMESTIC
 PUMP ROOM).
 SEC. 107.2.1.2 CITY AMENDMENTS.
  
 RESPONSE:
 (1)REVISED FINAL SURVEY SHOWS 14.24 (NAVD) FINISH FLOOR
 ELEVATION AT TRASH ROOM. THIS ELEVATION IS BELOW THE
 DESIGN FLOOD ELEVATION OF 14.7 (NAVD) SPECIFIED BY THE
 DESIGNER OF RECORD. SEE SHEET A-2.1 FOR PROPOSED
 ELEVATION (16.25 NGVD). COORDINATE WITH THE DESIGNER OF
 RECORD AND SHOW COMPLIANCE WITH THE REQUIRED FINISH
 ELEVATION.
 SEC. 1612.4 FBC-BUILDING. SEC. 1.5.2 ASCE 24.
  
 (2)CLARIFY WHY DOMESTIC PUMP ROOM SAYS F.F.E.=14.71
 SINCE THERE IS AN SPOT ELEVATION OF 14.61 SHOWN AT THE
 ENTRY OF THIS ROOM.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (3)CLARIFY WHY LOADING AREA F.F.E.=14.12 AND THERE IS
 AN SPOT ELEVATION OF 14.62 SHOWN AT THE ENTRANCE OF THE
 LOADING AREA.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 (B)OK.
 (C)OK.
  
 ORIGINAL COMMENT:
 (D)ACCORDING TO FINAL SURVEY SUBMITTED IT LOOKS LIKE
 THE TOP OF ATTACHED GARAGE ELEVATION IS TAKEN AT A
 MIDPOINT OF THE GARAGE RAMP. THE LOWEST ELEVATION OF
 THE GARAGE IS AT THE ENTRANCE OF THE GARAGE. REVISE AS
 REQUIRED.
  
 RESPONSE:
 GARAGE ELEVATION WAS CHANGED, BUT THE LOCATION WHERE
 THIS ELEVATION IS SHOWN IS MISLEADING. THIS ELEVATION
 IS SHOWN AT MID POINT OF THE GARAGE. THIS GARAGE HAS
 DIFFERENT LEVELS AND THE POINT WHERE THE REVISED
 ELEVATION IS SHOWN IS HIGHER THAN THE NUMBER SHOWN.
 TYPICALLY, THE ELEVATIONS ARE MARKED AT THE POINT WHERE
 THE ELEVATION IS TAKEN. REVISE AS REQUIRED TO AVOID
 CONFLICTS. SEC. 107.2.1 CITY AMENDMENTS.
  
 NEW COMMENT TO THIS ITEM:
 (E)BASED ON THE REVISED FINAL SURVEY IT LOOKS LIKE THE
 LOWEST ELEVATION OF MACHINERY/EQUIPMENT IS NOT THE
 GENERATOR PAD. THE EQUIPMENT LOCATED IN THE ROOMS
 ADJACENT TO THE LOADING AREA SEEM TO BE LOWER THAN THE
 GENERATOR PAD. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (F)OK.
 (G)OK.
 (H)OK.
  
 ORIGINAL COMMENT:
 2- PROVIDE PHOTOS SHOWING THE VENTS SPECIFIED ON ITEM
 A9(B).
 NOTE: COORDINATE WITH VENTS SHOWN ON SHEET A.2.1 AND
 DETAILS 4 AND 8 ON SHEET A-8.1.1. THERE IS A VENT
 INSIDE THE GARAGE CONNECTING TO THE OUTSIDE WALL. THE
 OTHER VENT CONSIDERED BY THE ARCHITECT OF RECORD IS THE
 ENTRANCE TO THE GARAGE. SHOW ALL VENTS. SEE ITEM A6
 FEMA ELEVATION CERTIFICATE INSTRUCTIONS.
 ALSO, ALL PHOTOS NEED TO BE AT LEAST 3"X3". REVISE
 PHOTO THREE ON PAGE 6 OF 6.
  
 SEE ARCHITECT'S REVISION #8 ON PLANS AND REVISION
 #19110684 CITY RECORDS.
  
 RESPONSE:
 (1)ONLY THE INSIDE VENT WAS SHOWN. NEED PHOTO SHOWING
 THE OUTSIDE VENT THAT CONNECTS TO THE INSIDE VENT.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 (2)VENT SHOWN ON THE PHOTO DOESN'T SEEM TO MATCH THE
 ONE DESIGNED BY THE DESIGNER OF RECORD. SEE SHEET SHEET
 A.2.1 AND DETAILS 4 AND 8 ON SHEET A-8.1.1. DESIGNER OF
 RECORD NEEDS TO REVISE VENT DESIGN OR CONTRACTOR NEEDS
 TO INSTALL VENT THAT MATCHES THE ONE DESIGNED BY THE
 ARCHITECT OF RECORD.
 SEC. 107.2.1 CITY AMENDMENTS.
  
  
 3- OK.
  
 NEW COMMENT:
 4- ITEM A9(C) WAS REVISED. THIS ITEM IS FOR THE NET
 AREA OF FLOOD OPENINGS. AREA SHOWN IS WAY TOO HIGH
 COMPARED TO THE ONE SPECIFIED BY THE ARCHITECT OF
 RECORD ON SHEET SHEET A.2.1 AND DETAILS 4 AND 8 ON
 SHEET A-8.1.1. PLEASE COORDINATE WITH ARCHITECT AND
 REVISE AS REQUIRED. ONLY THE AREA BELOW THE DESIGN
 FLOOD ELEVATION COUNTS. ALSO, NEED TO SPECIFY THE
 ACTUAL NET AREA (EXCLUDING VENT FRAME)OF THE INSTALLED
 VENTS.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER