2021-05-06 15:49:35 | FINAL ELEVATION CERTIFICATE REVIEW COMMENTS: |
| SUBMITTAL #21041684 |
| |
| 1- REVISE INFORMATION ENTERED IN SECTION C2: |
| (A) THERE IS NO INFORMATION IN THE SURVEY FOR THE |
| ELEVATION AT THE LOADING AREA ON THE NORTH SIDE OF THE |
| BUILDING. ACCORDING TO PLANS, THE ELEVATION AT THE |
| ENTRANCE OF THE LOADING AREA IS LOWER THAN THE REST OF |
| THE FLOOR. THIS LOOKS LIKE THE TOP OF BOTTOM FLOOR. |
| REVISE AS REQUIRED. |
| PROVIDE FINAL SURVEY SHOWING ELEVATIONS IN THE LOADING |
| AREA. (INCLUDE THE FIRE PUMP ROOM, TRASH ROOM, DOMESTIC |
| PUMP ROOM). |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| (B) COORDINATE WITH ITEM #1 ABOVE. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| (C)OK. |
| |
| (D)ACCORDING TO FINAL SURVEY SUBMITTED IT LOOKS LIKE |
| THE TOP OF ATTACHED GARAGE ELEVATION IS TAKEN AT A |
| MIDPOINT OF THE GARAGE RAMP. THE LOWEST ELEVATION OF |
| THE GARAGE IS AT THE ENTRANCE OF THE GARAGE. REVISE AS |
| REQUIRED. |
| ALSO, REVISE ELEVATION 12.4. ACCORDING TO SURVEY THIS |
| ELEVATION IS 12.38. THE ELEVATION NEEDS TO BE ENTERED |
| TO THE NEAREST TENTH OF A FOOT AS REQUIRED BY ITEM C2 |
| OF FEMA ELEVATION CERTIFICATE INSTRUCTIONS. THEREFORE, |
| THE CORRECT ROUNDING WILL BE 12.0 NOT 12.4. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| (E)OK. |
| |
| (F)SURVEY SUBMITTED DOESN'T SHOW THE LOWEST ADJACENT |
| GRADE NEXT TO THE BUILDING. UNABLE TO VERIFY. PROVIDE |
| SURVEY WITH INFORMATION. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| (G)SURVEY SUBMITTED DOESN'T SHOW THE HIGHEST ADJACENT |
| GRADE NEXT TO THE BUILDING. UNABLE TO VERIFY. PROVIDE |
| SURVEY WITH INFORMATION. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| (H) SURVEY SUBMITTED DOESN'T SHOW ELEVATION OF DECK OR |
| STAIRS. UNABLE TO VERIFY. PROVIDE SURVEY WITH |
| INFORMATION. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| 2- PROVIDE PHOTOS SHOWING THE VENTS SPECIFIED ON ITEM |
| A9(B). |
| NOTE: COORDINATE WITH VENTS SHOWN ON SHEET A.2.1 AND |
| DETAILS 4 AND 8 ON SHEET A-8.1.1. THERE IS A VENT |
| INSIDE THE GARAGE CONNECTING TO THE OUTSIDE WALL. THE |
| OTHER VENT CONSIDERED BY THE ARCHITECT OF RECORD IS THE |
| ENTRANCE TO THE GARAGE. SHOW ALL VENTS. SEE ITEM A6 |
| FEMA ELEVATION CERTIFICATE INSTRUCTIONS. |
| ALSO, ALL PHOTOS NEED TO BE AT LEAST 3"X3". REVISE |
| PHOTO THREE ON PAGE 6 OF 6. |
| |
| SEE ARCHITECT'S REVISION #8 ON PLANS AND REVISION |
| #19110684 CITY RECORDS. |
| |
| |
| 3- FINAL SURVEY SUBMITTED: |
| A) PROVIDE FINAL SURVEY SHOWING ALL THE ELEVATIONS |
| REFERENCED IN THE ELEVATION CERTIFICATE. COORDINATE |
| WITH ITEM #1. |
| SEC. 107.2.1.2 CITY AMENDMENTS. |
| |
| B) THE POOL SHOWS A TOP OF POOL FORM-BOARD ELEVATION OF |
| 14.49'. CLARIFY WHY IT IS A FORM-BOARD ELEVATION IF |
| THIS IS A FINAL SURVEY. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |