Plan Review Notes
Plan Review Notes For Permit 21041663
Permit Number 21041663
Review Stop B
Sequence Number 2
Notes
Date Text
2021-06-30 08:33:43PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER PX3169 1&2 FAMILY - SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. PROVIDE COVER SHEETS FO FL25574.
  
 THE COVER SHEET PROVIDES THE APPROVAL NUMBER, CODE
 VERSION, AND STATUS, FBC R 301.
 (COVER SHEETS ARE NOT REQUIRED FOR MIAMI DADE NOAS.)
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 2. WALL PRESSURE CALCULATOR SUBMITTED ON 6/17/21 IS
 BASED ON ASCE 7-10. THIS DOCUMENT HAS EXPIRED. PROVIDE
 DESIGN WIND LOADS PER ASCE 7-16.
 PROVIDE SITE SPECIFIC DESIGN WIND LOADS PER FBC CHPT 16
 AND ASCE 7-16. CALCULATIONS SHALL BE PREPARED BY
 FLORIDA LICENSED DESIGN PROFESSIONAL.
 1609.1.1DETERMINATION OF WIND LOADS.
 WIND LOADS ON EVERY BUILDING OR STRUCTURE SHALL BE
 DETERMINED IN ACCORDANCE WITH CHAPTERS 26 TO 30 OF ASCE
 7. WIND SHALL BE ASSUMED TO COME FROM ANY HORIZONTAL
 DIRECTION AND WIND PRESSURES SHALL BE ASSUMED TO ACT
 NORMAL TO THE SURFACE CONSIDERED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  
  
  
  
  