2021-05-07 11:12:57CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW
  
 1) NEW RISER ALSO SHOWS A CHANGE IN THE SIZE OF
 CONDUCTOR FROM METER TO 200 AMPS SE RATED ATS AMD TO
 200 AMPS PANEL.
 NEW DIAGRAM NOW SHOWS A #2/0 CONDUCTOR INSTEAD OF #3/0.
 THE 2/0 IS RATED FOR ONLY 175 AMPS AND PER NEC
 310.15(B)(7) THE AMPACITY
 OF THESE CONDUCTORS CANNOT BE DERATED SINCE THEY DO NOT
 SUPPLY THE ENTIRE LOAD TO THE HOUSE. MINIMUM SIZE SHALL
 BE #3/0 CU AS SPECIFIED IN THE
 ORIGINAL RISER DIAGRAM.
  
 SINCERELY,
  
 ENRIQUE QUINONEZ PE
 ELECTRICAL PLANS EXAMINER