Plan Review Notes For Permit 21041659 |
Permit Number |
21041659 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-07 11:12:57 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED. SEE NEW COMMENTS BELOW | | | | 1) NEW RISER ALSO SHOWS A CHANGE IN THE SIZE OF | | CONDUCTOR FROM METER TO 200 AMPS SE RATED ATS AMD TO | | 200 AMPS PANEL. | | NEW DIAGRAM NOW SHOWS A #2/0 CONDUCTOR INSTEAD OF #3/0. | | THE 2/0 IS RATED FOR ONLY 175 AMPS AND PER NEC | | 310.15(B)(7) THE AMPACITY | | OF THESE CONDUCTORS CANNOT BE DERATED SINCE THEY DO NOT | | SUPPLY THE ENTIRE LOAD TO THE HOUSE. MINIMUM SIZE SHALL | | BE #3/0 CU AS SPECIFIED IN THE | | ORIGINAL RISER DIAGRAM. | | | | SINCERELY, | | | | ENRIQUE QUINONEZ PE | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|