Plan Review Notes For Permit 21041657 |
Permit Number |
21041657 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-06-10 12:09:29 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR EMAIL [email protected] AND REQUEST | | THAT IT BE CONVERTED TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL16709-R7 SELECTED SYSTEM NO W-5; EXPOSURE | | (C); ENCLOSURE (ENCLOSED); ROOF HEIGHT (20 < H < 30); | | ULTIMATE WIND SPEED (160), IS NOT CORRECT. THE ULTIMATE | | WIND SPEED FOR THE LISTED ADDRESS IS 170 (MPH). PLEASE | | SELECT THE CORRECT OPTIONS; CONSIDER USING FL16709-R8 | | SYSTEM NO. W-5; EXPOSURE C; ENCLOSED; 20 < H < 30; 170 | | (MPH). | | |
|