2021-05-11 14:55:26 | 05/11/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON SHEET P0.00; |
| |
| A. PLEASE ADD THE ACCESSIBILITY CODE IN THE CURRENT |
| CYCLE UNDER APPLICABLE CODES PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| B. PLEASE PROVIDE DETAIL FOR THE SLAB REPAIR PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 2. ON SHEET P1.01; |
| |
| A. THE EXISTING SANITARY IS CAPPED OFF IN THE ADJACENT |
| SIDE, AND THERE IS NO SANITARY FOR THE FUTURE TENANT IN |
| SUITE A12. PLEASE SHOW OR GIVE AN OPTION ON HOW THE |
| SANITARY SYSTEM WILL BE PROVIDED FOR A12 UNITS PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| B. PLEASE SHOW A CLEAN-OUT FOR GW ENTERING THE BUILDING |
| WITHIN TEN FEET PER THE 708.1.3 BUILDING DRAIN AND |
| BUILDING SEWER JUNCTION. |
| |
| 3. ON SHEET P2.00, A SEPARATE PERMIT SHALL BE OBTAINED |
| FOR THE GREASE INTERCEPTOR; PLEASE PROVIDE A NOTE ON |
| THIS SHEET PER THE WPB AMENDMENTS TO THE FBC SEC. |
| 105.1. |
| |
| 4. PLEASE PROVIDE DOCUMENTATION THAT THE EXISTING |
| ACCESSIBILITY RESTROOM COMPLIES WITH THE CURRENT CODE |
| OF ITS CYCLE OR GIVE A PAGE TO REFERENCE IN THE FIELD |
| OF THE DIMENSION AND APERTURES PER THE WPB AMENDMENTS |
| TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |