2021-05-07 09:10:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21041643
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ACCORDING TO SHEET A1.1.1 THE NEW SEPARATING WALL IS
 A 1-HOUR RATED PARTITION, PLEASE SHOW DAMPERS IN EACH
 DUCT THAT IS PENETRATING THIS NEW FIRE PARTITION OR
 SHOW WHY IT ISN?T REQUIRED. FBC M 607.5.3
  
 2) IT APPEARS THAT THE NEW RATED WALL IS GOING TO BE
 INSTALLED IN THE MIDDLE OF THE EXISTING 16X10
 ENVIRONMENTAL AIR EXHAUST DUCT. PLEASE SHOW HOW THIS
 DESIGN IS POSSIBLE. FBC 107.2.1
  
 3) THE 10X10 DUCT SHOWN FOR FUTURE TYPE II EXHAUST IS
 BEING TERMINATED INTO THE ENVIRONMENTAL AIR EXHAUST
 DUCT. PLEASE REMOVE THIS FROM THIS PROJECT AND SHOW IT
 ON THE TENANT UPFIT. WE CAN NOT APPROVE THIS DESIGN AS
 TYPE II HOOD EXHAUST WOULD NOT MEET THE DEFINITION OF
 ENVIRONMENTAL AIR AND WOULD NEED ITS OWN EXHAUST DUCT
 SYSTEM. FBC M CHAPTER 2 DEFINITION OF ENVIRONMENTAL
 AIR; FBC M 506.4
  
 4) PLEASE PROVIDE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THIS NEW TENANT SPACE. FBC EC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  