2021-05-24 15:25:39 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | THERE ARE INDICATIONS A MULTIPLE WALLS BEING REMOVED | | WITH NEW SPACES CREATED. THE BUILDING HAS AN EXISTING | | FIRE SPRINKLER AND FIRE ALARM SYSTEM. | | | | THERE IS NO INDICATION OF FIRE SPRINKLER NOR FIRE ALARM | | WORK. | | | | | | 1) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | 2) ANY AND ALL WORK ON THE FIRE ALARM AND/OR FIRE | | SPRINKLER SYSTEMS, INCLUDING DEMO, SHALL BE DONE UNDER | | SEPARATE PERMITS AND SHOP DRAWINGS. | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | 3) THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT. | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] |
|