Review Stop FIRE
Sequence Number 1
Notes
Date Text
2021-05-27 15:36:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS IN-FILL OF WALL OPENINGS INDICATED. THE
 WALL ARE REQUIRED TENANT 1HR. FIRE RATED WALL
 SEPARATIONS. THERE IS NO INDICATIONS OF A LISTED FIRE
 RATED WALL ASSEMBLY THAT MEETS THE EXISTING FIRE RATED
 WALL ASSEMBLY.
  
 PLEASE REVIEW AND PROVIDE A LISTED FIRE RATED WALL
 ASSEMBLY THAT MEETS THE EXISTING ONE.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  