2021-07-13 14:18:2507/13/21 2ND PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 SECOND REQUEST, NON OF THE COMMENTS WHERE ADDRES!
  
 1. PLEASE PROVIDE INFORMATION AND PLANS CORRESPONDING
 TO THE TYPE OF OCCUPANCY AND ACCESSIBILITY PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 2. ON SHEET A-2;
  
 A. PLEASE PROVIDE A PLUMBING RISER DIAGRAM FOR THE
 BATHROOM AND WASHING MACHINE AND KITCHEN PER THE WPB
 AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL
 PLUMBING.
  
 B. PLEASE GIVE THE NUMBER OF OCCUPANT'S NUMBER, TYPE,
 AND CALCIFICATION TO DETERMINE THE MINIMUM FIXTURES. IF
 COMMERCIAL OCCUPANCY WILL BE USED.
  
 3. THE PLANS SHOW A STACKABLE UNIT. IF THIS IS A
 COMMERCIAL UNIT, IT WILL NEED A LINT TRAP AT THE
 WASHING MACHINE; PLEASE PROVIDE THE SPECIFICATION AND
 SHOW IT ON ISOMETRIC PER THE 2020 FC SEC P 1003.6
 CLOTHES WASHER DISCHARGE INTERCEPTOR.
  
 4. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE
 ACCESSIBLE WITHOUT MOVING THE UNIT WITHIN REACH PER THE
 2020 FBC SEC. P 606.3 ACCESS TO VALVES.
  
 5. ON SHEET P-2;
 A. THIS UNIT IS CONSTRUCTED UNDER THE REQUIREMENTS OF
 THE FAIR HOUSING ACT. PLEASE INDICATE ON THE PLANS
 WHICH DESIGN SPECIFICATIONS WILL BE USED AND WAS USED
 IN THE ORIGINAL DESIGN OF UNIT IN THE FIRST FLOOR
 BATHROOM. THE LEVEL OF ACCESSIBILITY CANNOT BE
 DECREASED. THE PLANNED ALTERATIONS TO THE DOWN STAIRS
 BATH DO NOT COMPLY WITH THE REQUIREMENTS OF THE FAIR
 HOUSING ACT GUIDELINES.
  
 B. PLEASE SHOW DIMENSION BETWEEN FIXTURES INSTALLATION
 TO CONFORM TO THE 2020 FBC SEC. P 405.3.1 WATER CLOSET,
 LAV AND P 421.4. SHOWER.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR