2021-06-10 12:42:59 | 06/10/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE PROVIDE INFORMATION AND PLANS CORRESPONDING |
| TO THE TYPE OF OCCUPANCY THIS UNIT WILL BE. A KITCHEN |
| IS NOT SHOWN ON PLAN PLEASE PROVIDE ON PLANS PER THE |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| |
| 2. ON SHEET A-2; |
| |
| A. PLEASE PROVIDE A PLUMBING RISER DIAGRAM FOR THE |
| BATHROOM AND WASHING MACHINE PER THE WPB AMENDMENTS TO |
| THE FBC SEC. 107.3.5.3 (12) RESIDENTIAL PLUMBING. |
| |
| B. PLEASE GIVE THE NUMBER OF OCCUPANTS NUMBER, TYPE, |
| AND CALCIFICATION TO DETERMINE THE MINIMUM FIXTURES IF |
| APPLICABLE. |
| |
| 3. THE PLANS SHOW A STACKABLE UNIT. IF THIS IS A |
| COMMERCIAL UNIT, IT WILL NEED A LINT TRAP AT THE |
| WASHING MACHINE; PLEASE PROVIDE THE SPECIFICATION AND |
| SHOW IT ON ISOMETRIC PER THE 2020 FC SEC P 1003.6 |
| CLOTHES WASHER DISCHARGE INTERCEPTOR. |
| |
| 4. THE WASHING MACHINE SHUT-OFF VALVES SHALL BE |
| ACCESSIBLE WITHOUT MOVING THE UNIT WITHIN REACH PER THE |
| 2020 FBC SEC. P 606.3 ACCESS TO VALVES. |
| |
| 5. PLEASE SHOW DIMENSION BETWEEN FIXTURES INSTALLATION |
| TO CONFORM TO THE 2020 FBC SEC. P 405.3.1 WATER CLOSET, |
| LAV AND P 421.4. SHOWER. |
| |
| WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |