Plan Review Notes For Permit 21041499 |
Permit Number |
21041499 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-13 13:56:00 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) PROVIDE A SHOWER PAN DETAIL. FBC AMENDMENTS 107.2.1 | | | | 2) SPECIFY THE DIMENSIONS OF THE NEW SHOWER. FBC | | AMENDMENTS 107.2.1 | | | | 3) SHOW THE LOCATION OF THE SHOWER DRAIN. IS IT BEING | | MOVED FROM THE TUB DRAIN LOCATION? WILL THE FLOOR HAVE | | TO BE CUT? HOW WILL THE FIRE RATING OF THE FLOOR BE | | MAINTAINED? WHAT TYPE OF FIRESTOPPING WILL BE USED? FBC | | AMENDMENTS 107.2.1 | | | | 4) SPECIFY THE MATERIALS THAT WILL BE INSTALLED ON THE | | WALLS WHERE THE EXISTING TUB WAS. FBC AMENDMENTS | | 107.2.1 | | | | 5) IT APPEARS THAT A LICENSED BUILDING CONTRACTOR WILL | | BE REQUIRED TO PULL A SUB-PERMIT PERFORM THE WORK THAT | | IS NOT WITHIN THE SCOPE OF YOUR PLUMBING LICENSE. FBC | | AMENDMENTS 105 & FS 489 | | | | 6) THE COST FOR THIS WORK APPEARS TO UNDER VALUED. | | PROVIDE A COPY OF THE SIGNED CONTRACT. FBC AMENDMENTS | | 109.3 | | | | 7) PLEASE PROVIDE A RESPONSE LETTER THAT ADDRESSES EACH | | OF THE REVIEW COMMENTS. |
|