Plan Review Notes
Plan Review Notes For Permit 21041449
Permit Number 21041449
Review Stop B
Sequence Number 2
Notes
Date Text
2021-06-18 07:13:46SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC 2020 RESIDENTIAL 301:
  
 1. THE INSTALLATION SCHEDULE DOES NOT STATE WHAT THE
 SUBSTRATE IS - BLOCK, CONCRETE? IS THE SUBSTRATE THE
 SAME TOP AND BOTTOM?
  
 2. ELCO TAPCONS IS NOT ONE LISTED ON PAGES 10-11 OF THE
 PRODUCT APPROVAL SUBMITTED. REVISE THE INSTALLATION
 SCHEDULE TO STATE WHICH FASTENER IS PROPOSED, USING THE
 EXACT LANGUAGE AS ON THE PRODUCT APPROVAL.
  
 3. 1 1/2" EDGE DISTANCE IS PROPOSED, NOTE THAT THIS
 DIMENSION IS NOT ON THE ANCHOR SCHEDULES PAGES 10-11.
 1.25 WILL BE USED UNLESS THE ANCHOR SCHEDULE IS
 REVISED.
  
  
  
  