Plan Review Notes For Permit 21041429 |
Permit Number |
21041429 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-18 07:32:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | BUILDINGS WITH MORE THAN ONE CIRCUIT NEED A PANEL | | INSTALLED AND A GROUNDING ELECRODE SYSTEM, 225.30, | | 250.32 | | | | 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S) | | OR BRANCH CIRCUIT(S). (A) GROUNDING ELECTRODE. | | BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR | | BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR | | GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH | | PART III OF ARTICLE 250. THE GROUNDING ELECTRODE | | CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH | | 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING | | ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN | | 250.50 SHALL BE INSTALLED. | | | | 225.30 NUMBER OF SUPPLIES. A BUILDING OR OTHER | | STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER | | ON THE LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL | | BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS | | PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF | | THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE | | CONSIDERED A SINGLE CIRCUIT. | | | | PLEASE SUBMIT A RISER DIAGRM SHOWING THE LOCATION OF | | THE SERVICE. 215.5 |
|