2021-05-18 07:32:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 BUILDINGS WITH MORE THAN ONE CIRCUIT NEED A PANEL
 INSTALLED AND A GROUNDING ELECRODE SYSTEM, 225.30,
 250.32
  
 250.32 BUILDINGS OR STRUCTURES SUPPLIED BY A FEEDER(S)
 OR BRANCH CIRCUIT(S). (A) GROUNDING ELECTRODE.
 BUILDING(S) OR STRUCTURE(S) SUPPLIED BY FEEDER(S) OR
 BRANCH CIRCUIT(S) SHALL HAVE A GROUNDING ELECTRODE OR
 GROUNDING ELECTRODE SYSTEM INSTALLED IN ACCORDANCE WITH
 PART III OF ARTICLE 250. THE GROUNDING ELECTRODE
 CONDUCTOR(S) SHALL BE CONNECTED IN ACCORDANCE WITH
 250.32(B) OR (C). WHERE THERE IS NO EXISTING GROUNDING
 ELECTRODE, THE GROUNDING ELECTRODE(S) REQUIRED IN
 250.50 SHALL BE INSTALLED.
  
 225.30 NUMBER OF SUPPLIES. A BUILDING OR OTHER
 STRUCTURE THAT IS SERVED BY A BRANCH CIRCUIT OR FEEDER
 ON THE LOAD SIDE OF A SERVICE DISCONNECTING MEANS SHALL
 BE SUPPLIED BY ONLY ONE FEEDER OR BRANCH CIRCUIT UNLESS
 PERMITTED IN 225.30(A) THROUGH (E). FOR THE PURPOSE OF
 THIS SECTION, A MULTIWIRE BRANCH CIRCUIT SHALL BE
 CONSIDERED A SINGLE CIRCUIT.
  
 PLEASE SUBMIT A RISER DIAGRM SHOWING THE LOCATION OF
 THE SERVICE. 215.5