2022-10-19 12:07:17 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL25621.05.1-R2 COVERS MULTIPLE INSTALLATION |
| OPTIONS TO MEET DESIGN UPLIFT PRESSURES. PLEASE SELECT |
| CORRECT INSTALLATION OPTIONS FROM PAGE #2 OF THE |
| EVALUATION REPORT & PAGE #3 SELECT LOAD TABLE FOR |
| STRUCTURES LOCATED IN EXPOSURE B, C, OR D AREA; HAVE |
| EITHER A FLAT ROOF, OR GABLE/HIP ROOF WITH MAX SLOPE OF |
| 12:12; HAVE A MEAN ROOF HEIGHT 30 FEET OR LESS; CIRCLE |
| CORRECT WIND SPEED & INSTALLATION METHODS FOR ZONES 1, |
| 2 & 3. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE |
| CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. |
| DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN |
| PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |