Plan Review Notes
Plan Review Notes For Permit 21041411
Permit Number 21041411
Review Stop G
Sequence Number 2
Notes
Date Text
2021-05-21 13:06:4905/21/21 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SECOND REQUEST; THE ADDRESS FOR THIS STRUCTURE HAS
 NO CHANGE OF OCCUPANCY IN THE CITY RECORDS AND NO
 BUILDING PERMIT ON FILE. ANY OWNER OR AGENT AUTHORIZED
 IN ACCORDANCE WITH FLORIDA STATUTE 489 WHO INTENDS TO
 CONSTRUCT, ENLARGE, ALTER, REPAIR, MOVE, DEMOLISH, OR
 CHANGE THE OCCUPANCY OF A BUILDING OR STRUCTURE, OR TO
 ERECT, INSTALL, ENLARGE, ALTER, REPAIR, REMOVE, CONVERT
 OR REPLACE ANY IMPACT-RESISTANT COVERINGS, ELECTRICAL,
 GAS, MECHANICAL, PLUMBING OR FIRE PROTECTION SYSTEM, OR
 ACCESSIBLE OR FLOOD-RESISTANT SITE ELEMENT, THE
 INSTALLATION OF WHICH IS REGULATED BY THIS CODE, OR TO
 CAUSE ANY SUCH WORK TO BE DONE, SHALL FIRST MAKE
 APPLICATION TO THE BUILDING OFFICIAL AND OBTAIN THE
 REQUIRED PERMIT PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 2. SECOND REQUEST; PLEASE PROVIDE A DESCRIPTIVE SCOPE
 OF WORK THAT WILL BE PERFORMED ON THE PLANS, LIST
 FIXTURE APPURTENANCES BEING INSTALLED, AND THE EXTENT
 OF WORK YOU ARE DOING PER THE WPB AMENDMENTS TO THE FBC
 SEC. 101.2 SCOPE.
  
 3. SECOND REQUEST; THE CLAIMED VALUE APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION. PLEASE PROVIDE A
 BONA FIDE SIGNED CONTRACT PER THE WPB AMENDMENTS TO THE
 FBC SEC. 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE
 OPINION OF THE BUILDING OFFICIAL, THE CLAIMED VALUATION
 OF THE BUILDING, ALTERATION, STRUCTURE, ELECTRICAL,
 GAS, MECHANICAL, OR PLUMBING SYSTEMS APPEARS TO BE
 UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE
 DENIED UNLESS THE APPLICANT CAN SHOW DETAILED, QUANTITY
 ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS (EXCLUDING
 LAND VALUE) TO MEET THE APPROVAL OF THE BUILDING
 OFFICIAL. FOR PERMITTING PURPOSES, THE VALUATION OF
 BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE
 TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL,
 INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND
 DESIGN FEES, MARKETING COSTS, OVERHEAD, AND PROFIT,
 EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY
 INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL
 CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT,
 MEANS, ETC.), AS PUBLISHED BY INTERNATIONAL CODE
 CONGRESS. THE BUILDING OFFICIAL SHALL SET THE FINAL
 BUILDING PERMIT VALUATION.
  
 4. PLEASE SHOW EMERGENCY HOOD SHUT DOWN SHUTOFF VALVE
 AND IT SHALL BE BELOW THE CEILING. THE MANUAL SHUTOFF
 VALVE SHALL BE UPSTREAM. UNION TO BE DOWNSTREAM OF
 MANUAL VALVE. SECS. 10.4, 10.5 OF NFPA 96-08. AT LEAST
 ONE MANUAL ACTUATION DEVICE SHALL BE LOCATED A MINIMUM
 OF 3 M (10 FT) AND A MAXIMUM OF 6 M (20 FT) FROM THE
 PROTECTED HOOD EXHAUST SYSTEM(S) WITHIN A PATH OF
 EGRESS OR AT AN ALTERNATIVE LOCATION ACCEPTABLE TO THE
 AHJ.
  
 5. SECOND REQUEST; PLEASE SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2020 FBC FG SECS. 402.4.1, 402.4.2.
  
 6. SECOND REQUEST; SHOW THE TYPE OF PIPE MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING EHD
 NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF
 APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 7. SECOND REQUEST; TYPE OF GAS (LP OR NATURAL) PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 8. SECOND REQUEST; INDICATE THE DELIVERY PRESSURE (PSI)
 OF THE SYSTEM ON THE PLAN PER THE 2020 FBC FG SEC.
 402.2.
  
 9. SECOND REQUEST; SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2020 FBC FG SEC.305.1.
  
 10. SECOND REQUEST; GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES/EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION PER THE 2020 FBC FG SECS. 402.2 AND 301.3.
  
 11. SECOND REQUEST; LIST THE BTU LOAD OF EACH APPLIANCE
 AND THE TOTAL BTU LOAD ON THE SYSTEM. REFER TO THE 2020
 FBC FG SECS. 401.8 THROUGH 402.6.1 AND TABLES 402.4 (1)
 THROUGH 402.4 (37).
  
 12. SECOND REQUEST; SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY (GAS METER / MP REGULATOR / LP TANK) TO THE
 MOST REMOTE OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE 2020 FBC FG SEC. 402.4.1.
  
 13. SECOND REQUEST; PLEASE SUBMIT THE SIZING TABLE USED
 IN THE DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON
 BOTH SETS OF PLANS LISTING THE SIZING TABLES FROM GAS
 CODES OR ANOTHER STANDARD THAT WERE USED IN THE DESIGN
 OF THIS SYSTEM PER THE 2020 FBC FG SEC. 402.3.
  
 14. PLEASE SUBMIT CALCULATIONS FOR COMBUSTION AIR PER
 THE 2020 FBC FG SEC. 304.1. WHERE IS COMBUSTION AIR
 PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR PER THE 2020 FBC FG SEC. 304.9.3.
 COMBINED COMBUSTION AIR AND VENTILATION AIR SYSTEM.
  
 15. SECOND REQUEST; PLEASE SUBMIT THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC FG
 SEC. 410.1.
  
 16. SECOND REQUEST; PLEASE SHOW ALL UNIONS IN FRONT OF
 REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC FG SEC
 410.2.
  
 17. SECOND REQUEST; SHOW DRIP LEG ON EQUIPMENT
 INSTALLED, EXCEPT FOR APPLIANCES, RANGE, DRYERS & OD
 GRILLS PER THE 2020 FBC FG 408.2.
  
 18. SECOND REQUEST; PLEASE PROVIDE THE SIGNATURE OF ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING
 DATA THAT SHALL BEAR THE PRINTED NAME AND SIGNATURE OF
 THE PERSON RESPONSIBLE FOR THE DESIGN PER THE WPB
 AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  