2021-08-04 06:53:09 | PETER E VALENTI |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561?805?6673 |
| |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A |
| DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303: |
| |
| 1. UTILITY RELEASE ? FLORIDA POWER & LIGHT (ELECTRIC) |
| RELEASE OF SERVICE CONFIRMATION. |
| |
| (CITY RESPONSE: PLEASE PROVIDE THE FPL RELEASE ON THE |
| FPL LETTERHEAD RELEASE FORM.) |
| |
| |
| 3. UTILITY RELEASE ? CITY OF WEST PALM BEACH WATER |
| DEPARTMENT, REQUEST FOR METER PULL, ON THEIR FORM |
| "DEMOLITION APPLICATION" |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT?SERVICES/FORMS/B |
| UILDING?PERMIT?FORMS |
| |
| IF A WATER TRUCK IS DESIRED FOR WATERING DOWN SITE, |
| DETAILS WILL BE REQUIRED. |
| |
| IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED, |
| THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM. |
| IF A BACKFLOW PREVENTER DEVICE HAS BEEN SELECTED FOR |
| THE WATER DOWN METHOD AND A PERMIT HAS BEEN OBTAINED ? |
| BEFORE SCHEDULING THE FINAL INSPECTION, THE BACKFLOW |
| DEVICE NEEDS TO BE TESTED AND CERTIFIED BY THE CITY?S |
| UTILITIES DEPT, 561?822?2244. |
| |
| FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO |
| 561?822?2183. |
| |
| (CITY RESPONSE: PLEASE PROVIDE THE PUBLIC UTILITIES |
| DEMOLITION APPLICATION THAT HAS BEEN COMPLETED AND |
| RETURNED BY THE PUBLIC UTILITIES DEPARTMENT AND PROVIDE |
| THE PUBLIC UTILITIES DEPARTMENT UPDATED APPROVAL FOR |
| THE EXISTING BACKFLOW PREVENTER DEVICE.) |
| |