Plan Review Notes
Plan Review Notes For Permit 21041287
Permit Number 21041287
Review Stop G
Sequence Number 1
Notes
Date Text
2021-04-28 11:27:3204/28/21 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF
 THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH
 FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA
 STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC.
 107.1 GENERAL.
  
 2. SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR THE RANGE TO VERIFY
 COMPLIANCE WITH 2020 FBC RES. SEC. G2408.1.
  
 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020
 FBC RES. SEC. G2413.2 AND G2404.3.
  
 4. SUBMIT A SIZING TABLE USED IN THE DESIGN FOR THE GAS
 SYSTEM OR PLACE A NOTE ON BOTH SETS OF PLANS LISTING
 THE SIZING TABLES FROM GAS CODES OR ANOTHER STANDARD
 USED IN THE DESIGN OF THIS SYSTEM PER THE 2020 FBC RES.
 SEC. G2413.3.
  
 5. PLEASE SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR
 THE PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 BUILDING'S EXTERIOR SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2020 FBC RES. SEC. G2421.1.
  
 6. THE CLAIMED VALUE APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION. PLEASE PROVIDE A BONA FIDE SIGNED
 CONTRACT PER THE WPB AMENDMENTS TO THE FBC 109.3.
 BUILDING PERMITS VALUATIONS.
  
 7. PLEASE SHOW THE DISTANCE OF THE LOCATION OF THE
 TANK-LESS WATER HEATER AND THE LOCATION AND DISTANCE OF
 ANY OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER
 HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS PER
 THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 8. THIS UNIT REQUIRES CONDENSATE, AND IT NEEDS TO BE 1'
 AWAY FROM THE STRUCTURE PER THE 2017 FBC SEC. R318.5.
 PLEASE PUT NOT ON PLANS.
  
 9. PIPES OR TANK-LEES NEED TO BE INSULATED WITH A
 MINIMUM R-3 PER THE 2017 FBC SEC. RE 403.5.3 PLEASE PUT
 A NOTE ON PLANS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  