Plan Review Notes
Plan Review Notes For Permit 21041277
Permit Number 21041277
Review Stop M
Sequence Number 3
Notes
Date Text
2021-08-17 14:32:193RD REVIEW FBC-2020 MECHANICAL
 PERMIT-21041277
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M4.0: PER FBC M 403.3.1.1 AND TABLE 403.3.1.1
 AND THE SQUARE FOOTAGE GIVEN FROM THE DESIGNER FOR THE
 OUTDOOR AIR CALCULATIONS THE FOLLOWING ARE THE REQUIRED
 OUTDOOR AIR CALCULATIONS REQUIRED FOR THE USE OF SPACE.
  
 KITCHEN: 490/1000 = .49 X 20 = 9.8 PEOPLE X 7.5 = 73.5
 + 490 X .12 = 132.3 REQUIRED FOR OUTDOOR AIR. KITCHEN
 EXHAUST: 490 X .7 = 343 CFM OF EXHAUST.
  
 WORKROOM WHICH IS LOCATED IN THE KITCHEN WITH NO
 SEPARATION MUST BE COUNTED AS KITCHEN: 229/1000 = .229
 X 20 = 4.58 PEOPLE X 7.5 = 34.35 + 229 X .12 = 61.83
 CFM OF REQUIRED OUTDOOR AIR. KITCHEN EXHAUST: 229 X .7
 = 160 CFM OF EXHAUST.
  
 SEATING AREA: 195/1000 = .195 X 70 = 13.65 PEOPLE X 7.5
 = 102.38 + 195 X .18 = 138.02 OF REQUIRED OUTDOOR AIR.
  
 KITCHEN PREP: 123/1000 = .123 X 20 = 2.46 PEOPLE X 7.5
 = 18.45 + 123 X .12 = 33.21 CFM OF REQUIRED OUTDOOR
 AIR. KITCHEN EXHAUST: 123 X .7 = 86 CFM OF EXHAUST.
  
 IF SQUARE FOOTAGE IS NOT NET PLEASE SEE FOOTNOTE (A )
 FBC M TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  