2021-08-17 14:32:19 | 3RD REVIEW FBC-2020 MECHANICAL |
| PERMIT-21041277 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M4.0: PER FBC M 403.3.1.1 AND TABLE 403.3.1.1 |
| AND THE SQUARE FOOTAGE GIVEN FROM THE DESIGNER FOR THE |
| OUTDOOR AIR CALCULATIONS THE FOLLOWING ARE THE REQUIRED |
| OUTDOOR AIR CALCULATIONS REQUIRED FOR THE USE OF SPACE. |
| |
| KITCHEN: 490/1000 = .49 X 20 = 9.8 PEOPLE X 7.5 = 73.5 |
| + 490 X .12 = 132.3 REQUIRED FOR OUTDOOR AIR. KITCHEN |
| EXHAUST: 490 X .7 = 343 CFM OF EXHAUST. |
| |
| WORKROOM WHICH IS LOCATED IN THE KITCHEN WITH NO |
| SEPARATION MUST BE COUNTED AS KITCHEN: 229/1000 = .229 |
| X 20 = 4.58 PEOPLE X 7.5 = 34.35 + 229 X .12 = 61.83 |
| CFM OF REQUIRED OUTDOOR AIR. KITCHEN EXHAUST: 229 X .7 |
| = 160 CFM OF EXHAUST. |
| |
| SEATING AREA: 195/1000 = .195 X 70 = 13.65 PEOPLE X 7.5 |
| = 102.38 + 195 X .18 = 138.02 OF REQUIRED OUTDOOR AIR. |
| |
| KITCHEN PREP: 123/1000 = .123 X 20 = 2.46 PEOPLE X 7.5 |
| = 18.45 + 123 X .12 = 33.21 CFM OF REQUIRED OUTDOOR |
| AIR. KITCHEN EXHAUST: 123 X .7 = 86 CFM OF EXHAUST. |
| |
| IF SQUARE FOOTAGE IS NOT NET PLEASE SEE FOOTNOTE (A ) |
| FBC M TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |