Plan Review Notes
Plan Review Notes For Permit 21041277
Permit Number 21041277
Review Stop P
Sequence Number 2
Notes
Date Text
2021-07-13 16:10:44CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017FAC=
 FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
 PLUMBING COMMENTS: DENIED
  
 PROVISO: WATER HEATER SCHEDULE INDICATES THAT AN
 ALTERNATE MANUFACTURER MAY BE SUBMITTED TO A/E FOR
 APPROVAL AND USE. PLEASE NOTE THAT A MANUFACTURER'S
 SPECIFICATION/INSTALLATION MANUAL SHALL BE SUBMITTED TO
 THE BUILDING DEPARTMENT FOR REVIEW AND APPROVAL AND IF
 DIFFERENT FROM THE CURRENT SCHEDULE A PLAN REVISION
 SHALL BE SUBMITTED TO THE BUILDING DEPARTMENT FOR
 REVIEW AND APPROVAL. BOTH SHALL BE ON SITE FOR FINAL
 INSPECTION. SEE WPB FBC 107.2.1 AND WPB FBC 107.3.4.1,
 DEFERRED SUBMITTALS. PROCEED AT YOUR OWN RISK.
  
 1. SECOND REQUEST: PER FBC 606.5 EXPOSED PIPES AND
 SURFACES. WATER SUPPLY & DRAINPIPES UNDER LAVATORIES
 AND SINKS SHALL BE INSULATED OR OTHERWISE CONFIGURED TO
 PROTECT AGAINST CONTACT. PLANS SHOW INSULATED P-TRAP
 BUT DO NOT INDICATE WATER SUPPLY PIPES.
  
 2.SECOND REQUEST: PER WPB FBC 107.2.1, PROVIDE
 STRUCTURAL DETAIL FOR MOUNTING OF THE TANKLESS WATER
 HEATER.
  
 3. SECOND REQUEST: PER FBC PL 419.5, COLD OR TEMPERED
 WATER SHALL BE DELIVERED FROM LAVATORIES AND GROUP WASH
 FIXTURES LOCATED IN PUBLIC TOILET FACILITIES PROVIDED
 FOR CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER
 SHALL BE DELIVERED THROUGH AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
 BMC RESPONSE: PLUMBING FIXTURE SCHEDULE HAS BEEN
 PROVIDED, WHICH DOES INDICATE THE TEMPERATURE LIMITING
 DEVICE FOR LAVATORIES AND HAND SINKS.
 NEW COMMENT: CANNOT FIND THE NOTED PLUMBING FIXTURE
 SCHEDULE ON THE PLANS.
  
 4.NEW COMMENT REGARDING THE WATER METER: PER WPB FBC
 107.2.1, PROVIDE MANUFACTURER?S
 SPECIFICATION/INSTALLATION MANUAL; ESPECIALLY SHOW
 INTEGRAL BACKFLOW PROTECTION, OR SPECIFY AND PROVIDE
 LEAD FREE BACKFLOW PREVENTER
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21041277 7402 S DIXIE HWY
  