Plan Review Notes For Permit 21041277 |
Permit Number |
21041277 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2021-07-06 13:32:02 | 2ND REVIEW FBC-2020 MECHANICAL | | PERMIT-21041277 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE | | FBC M- FLORIDA MECHANICAL CODE | | FBC EC- FLORIDA ENERGY CONSERVATION | | FBC FG- FLORIDA FUEL GAS | | FBC EX- FLORIDA EXISTING BUILDING CODE | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE PROVIDE AN OUTDOOR CALCULATION FOR EACH USE | | OF SPACE INDICATED ON SHEET A.01: ASSEMBLY-135 SQ. FT., | | KITCHEN-776 SQ. FT., STORAGE-235 SQ. FT. DO NOT SHOW | | THE HOOD EXHAUST OR MAKE UP AIR IN THIS OUTDOOR AIR | | CALCULATIONS AS THEY SHOULD BE SUBMITTED WITH CORRECTED | | RATES WHEN THE KITCHEN HOOD AND GREASE DUCT PERMIT IS | | SUBMITTED. FBC M 403.3.1.1 AND TABLE 403.3.1.1 | | | | 2) PLEASE ADD A NOTE ON THE MECHANICAL SCHEDULES SHEET | | THAT THE DESIGN AIR BALANCE REPORT WILL BE SUBMITTED | | WHEN COMPLETED. FBC M 508.1.2 | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|