2021-07-06 13:32:022ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21041277
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE AN OUTDOOR CALCULATION FOR EACH USE
 OF SPACE INDICATED ON SHEET A.01: ASSEMBLY-135 SQ. FT.,
 KITCHEN-776 SQ. FT., STORAGE-235 SQ. FT. DO NOT SHOW
 THE HOOD EXHAUST OR MAKE UP AIR IN THIS OUTDOOR AIR
 CALCULATIONS AS THEY SHOULD BE SUBMITTED WITH CORRECTED
 RATES WHEN THE KITCHEN HOOD AND GREASE DUCT PERMIT IS
 SUBMITTED. FBC M 403.3.1.1 AND TABLE 403.3.1.1
  
 2) PLEASE ADD A NOTE ON THE MECHANICAL SCHEDULES SHEET
 THAT THE DESIGN AIR BALANCE REPORT WILL BE SUBMITTED
 WHEN COMPLETED. FBC M 508.1.2
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  