Plan Review Notes
Plan Review Notes For Permit 21041277
Permit Number 21041277
Review Stop G
Sequence Number 2
Notes
Date Text
2021-07-13 15:02:40CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2020 7TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROL AND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017FAC=
 FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 2ND REVIEW
  
 GAS COMMENTS: DENIED
  
 1.WATER HEATER DETAIL; PER WPB FBC 107.2.1, CLARIFY THE
 FOLLOWING.
 SECOND REQUEST: SHOWS GAS- REGULATOR TO REDUCE PRESSURE
 TO 2 PSI. NOTE SHOULD STATE "REDUCE PRESSURE FROM 2 PSI
 TO .5 IN. WC" TO MATCH DESCRIPTION OF GAS REGULATOR ON
 P0.0
  
 2.SUBMIT CALCULATIONS FOR COMBUSTION AIR (NOT TO BE
 CONFUSED WITH MAKE-UP AIR.) PER THE FBC FG 304.1 CALCS
 ON P1.0;
 NEW COMMENT: AVAILABLE COMBUSTION AIR NOT NOTED. PER
 WPB FBC 107.2.1, INDICATE ON THE PLANS THE AVAILABLE
 COMBUSTION AIR (EXCESS OUTSIDE AIR MAY PROVIDE,PLEASE
 CLARIFY)
  
 3.GAS RISER: CLEARLY SHOW THE LOCATION OF ALL MP
 (STEP-DOWN) REGULATORS, VALVES AND UNIONS . A LISTED
 SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. FBC FG 409.4
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE NOTE AT
 PRESSURE REGULATOR DESCRIPTION ON P0.0; ?INSTALLATION
 OF GAS REGULATOR SHALL COMPLY WITH FBC FG 410.2?
  
 4.SECOND REQUEST: NOTES ON P0.0 ARE UNCLEAR AS TO
 INTENT. WHERE DOES THE 2PSI SYSTEM END AND THE LESS
 THAN 2PSI BEGIN. PER WPB FBC 107.2.1, CLARIFY. IS A
 REGULATOR TO BE PROVIDED IMMEDIATELY DOWNSTREAM OF THE
 FPU METER/ REGULATOR TO REDUCE PRESSURE AND THEN AN
 APPLIANCE REGULATOR TO BE SUPPLIED AT THE APPLIANCE;
 PER WPB FBC 107.2.1, CLARIFY. PROVIDE TABLES FOR SIZING
 FOR (2 PSI 1LB.PRESSURE DROP 402.4(5) #40 METALLIC) AS
 WELL AS (LESS THAN 2 PSI 402.4(3) 3? WC) NOTED ..
 CLEARLY INDICATE ON THE PIPING PLAN, THE 2 PSI PIPING
 AND WHICH GAS NOTE (2 OR 7) APPLIES TO WHICH SECTIONS
 OF PIPE.
 RESPONSE IS UNCLEAR
 ALSO UG IS NOT SPECIFIED-IF PE (PLASTIC PIPING) THEN
 PROVIDE TABLE AND TRACER WIRE W/DETAIL FOR TRANSITION
 TO AG.
  
 REVISED COMMENT
 P0.0 NOTES
 A.NOTED TABLE 402.4(3) ADDRESSES SCHEDULE 40 METALLIC
 PIPING LESS THAN 2PSI/.3 IN. WC/0.60 SG
 B.TABLE 402.4(2) NOT NOTED ADDRESSES SCHEDULE 40
 METALLIC PIPING LESS THAN 2PSI/.5 IN. WC/0.60 SG WHICH
 WOULD SEEM TO MATCH YOUR NOTE FOR THE GAS REGULATOR
 DESCRIPTION.
 C.NOTED PRESSURE 2PSI/1LB. PRESSURE DROP/0.60 SG FOR
 SCHEDULE 40 METALLIC PIPING IS COVERED BY TABLE
 402.4(5)
 E.REGARDING UG PIPE FROM METER TO BUILDING AND TO WATER
 HEATER,
 1) PLEASE REFER TO FBC FG 411.1, 411.1.1, 411.1.2(1),
 (2), (3) FOR PROTECTION OF STEEL PIPING FROM CORROSION
 (TABLE 402.4(5) WOULD APPLY). THIS OPTION REQUIRES
 STRINGENT AND POSSIBLY VERY EXPENSIVE REQUIREMENTS,
 2) OR REFER TO FBC FG 407.17, 407.17.1, 407.17.2,
 407.17.3 FOR PLASTIC PIPING. FBC FG TABLE 402.4(22)
 WOULD APPLY.
  
 5. SECOND REQUEST: SUBMIT MANUFACTURER'S SPECIFICATION
 SHEETS / INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE FBC FG 402.2, AND 301.3. GAS
 APPLIANCES SHALL BE LISTED AND LABELED. THE
 INSTALLATION MANUALS FOR ALL GAS APPLIANCES / EQUIPMENT
 SHALL BE ONSITE AT THE TIME OF INSPECTION. FBC FG 305.1
 NEW COMMENT: YOU MAY PER WPB FBC 107.2.1 AND WPB FBC
 107.3.4.1, PROVIDE AS A DEFERRED SUBMITTAL
 MANUFACTURER'S SPECIFICATION SHEETS / INSTALLATION
 MANUAL FOR ALL GAS EQUIPMENT TO VERIFY COMPLIANCE FBC
 FG 402.2, AND 301.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FBC FG 305.1. DOCUMENT SHALL BE SUBMITTED,
 APPROVED AND ON SITE PRIOR TO FINAL INSPECTION. PROCEED
 AT YOUR OWN RISK. PROVIDE NOTE ON THE PLANS.
  
 6.SECOND REQUEST: PER WPB FBC 107.2.1, SPECIFY THE
 UNDERGROUND PIPING MATERIAL AND PROVIDE SIZING TABLE.
 SEE REVISED COMMENT IN NOTE 4 ABOVE.
  
 7.PER WPB FBC 107.2.1, EXPLAIN THE DESIGNATION LNG ON
 THE RISER DIAGRAM. IS THIS LIQUIFIED NATURAL GAS?
 CLARIFY.
 NEW COMMENT: LIQUIFIED NATURAL GAS IS A STATE THAT IS
 USED FOR TRANSPORT (COMPRESSED BY REDUCING TEMPERATURE
 TO -250 DEGREES F AND MAINTAINED AT 4PSI) AND IS NOT
 DISTRIBUTED TO THE END USER IN THIS STATE. PER WPB FBC
 107.2.1, REVISE ALL DESIGNATION OF LNG TO NG FOR
 NATURAL GAS.
  
 8.PER WPB FBC 107.2.1, SHOW LOCATION OF THE FPU
 METER/REGULATOR ON THE PLAN VIEW.
 NEW COMMENT: PROVIDE GAS SHUT OFF VALVE AT CONSUMER
 SIDE OF METER REGULATOR PER FBC FG 409.2
 NEW COMMENT: PER WPB FBC 107.2.1, PROVIDE SPEC FOR GAS
 SHUT-OFF VALVES TO COMPLY WITH FBC FG SECTION 409.
  
 9.NEW COMMENT: KITCHEN EQUIPMENT SCHEDULE ON P2.0 MBTUS
 DOES NOT MATCH THE KITCHEN EQUIPMENT NOTED ON P0.0 GAS
 FIXTURE LOAD SUMMARY. PER WPB FBC 107.2.1, CLARIFY AND
 RECONCILE.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]