2021-06-01 13:34:15 | 1ST REVIEW FBC-2020 MECHANICAL |
| PERMIT-21041277 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE |
| FBC M- FLORIDA MECHANICAL CODE |
| FBC EC- FLORIDA ENERGY CONSERVATION |
| FBC FG- FLORIDA FUEL GAS |
| FBC EX- FLORIDA EXISTING BUILDING CODE |
| FBC RES- FLORIDA RESIDENTIAL BUILDING CODE |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PLACE NOTE ON THE DRAWINGS INDICATING THAT |
| ALL HOODS AND DUCTWORK WILL BE SUBMITTED AS A SEPARATE |
| PERMIT AND REVIEW AS THEY WILL NOT BE REVIEWED WITH THE |
| MECHANICAL SYSTEMS. |
| |
| 2) PLEASE PLACE A NOTE ON THE DRAWINGS INDICATING THAT |
| THE REFRIGERATION EQUIPMENT WILL BE SUBMITTED AS A |
| SEPARATE PERMIT AND REVIEW AS THEY WILL NOT BE REVIEWED |
| WITH THE MECHANICAL SYSTEMS. |
| |
| 3) PLEASE SHOW THAT ALL ROOFTOP EQUIPMENT WILL MEET FBC |
| M 304.11 FOR GUARDS ON THE ROOF. |
| |
| 4) PLEASE SHOW THAT THE RETURN IN THE KITCHEN MEETS THE |
| 10 FT CLEARANCE FROM COOKING APPLIANCES. FBC M 601.5 |
| EXCEPTION 1. |
| |
| 5) PLEASE PROVIDE AN OUTDOOR AIR CALCULATION FOR EACH |
| USE OF SPACE BASED ON FBC M 403.3.1.1 AND TABLE |
| 403.3.1.1 |
| |
| 6) PLEASE PROVIDE THE DESIGN AIR BALANCE REPORT. FBC M |
| 508.1.2 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |