2021-05-27 10:52:50CODES IN EFFECT
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020
 7TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW:
  
 1) SHEET E2.0 PANEL B SCHEDULE: CIRCUIT FOR DOAS-1 IS
 LISTED HAS HAVING A 200 AMPS BREAKER BUT CONDUCTOR SIZE
 IS ONLY #2 CU (AMPACITY = 115 AMPS). SHEET M4.0 (HVAC
 SCHEDULES) SPECS SHOWS MCA = 137.5 AMPS AND MOCP = 150
 AMPS FOR THE UNIT
 FAN SCHEDULE. ALSO SPECS DO NOT PROVIDE WHAT ARE TOTAL
 KVA LOADS FOR THIS UNIT (FANS, COMPRESORS, ETC.).
 PLEASE CLARIFY OR PROVIDE CORRECTIONS AS NEEDED. NEC
 2017
  
 2) IF TOTAL LOADS FOR DOAS-1 ARE DIFFERENT THAN 30 KVA
 PLEASE RECALCULATE LOADS FOR PANEL B
  
  
  