2021-05-27 10:52:50 | CODES IN EFFECT | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2020 | | 7TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | FAC = FLORIDA ADMINISTRATIVE CODE | | | | REVIEW STATUS: FAILED. PLEASE SEE COMMENTS BELOW: | | | | 1) SHEET E2.0 PANEL B SCHEDULE: CIRCUIT FOR DOAS-1 IS | | LISTED HAS HAVING A 200 AMPS BREAKER BUT CONDUCTOR SIZE | | IS ONLY #2 CU (AMPACITY = 115 AMPS). SHEET M4.0 (HVAC | | SCHEDULES) SPECS SHOWS MCA = 137.5 AMPS AND MOCP = 150 | | AMPS FOR THE UNIT | | FAN SCHEDULE. ALSO SPECS DO NOT PROVIDE WHAT ARE TOTAL | | KVA LOADS FOR THIS UNIT (FANS, COMPRESORS, ETC.). | | PLEASE CLARIFY OR PROVIDE CORRECTIONS AS NEEDED. NEC | | 2017 | | | | 2) IF TOTAL LOADS FOR DOAS-1 ARE DIFFERENT THAN 30 KVA | | PLEASE RECALCULATE LOADS FOR PANEL B | | | | | | | | ENRIQUE QUINONEZ PE | | ELECTRICAL PLANS EXAMINER | | DEVELOPMENT SERVICES | | CITY OF WEST PAM BEACH | | 401 CLEMATIS STREET, 1ST FLOOR | | WEST PALM BEACH, FL 33401 | | | | [email protected] | | | | FEEL FREE TO CONTACT ME IF YOU WISH TO DISCUSS, | | 561-805-6746. | | |
|