2021-05-18 11:29:23WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21041277
 ADD:7402 S. DIXIE HWY.
 CONT: THE OWEN GROUP
 TEL: 954-444-3008
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 18TH/ 2021
 ACTION: DENIED
 1) SHEET A.02 DEMOLITION & FLOOR PLAN:
  
 1A) THE FLOOR PLAN SHOWS A COUNTER WITH SEATING. THERE
 SEAMS TO BE A DISCREPANCY IN THE PLANS. THE FLOOR PLAN
 STATES 34-INCH-HIGH SEATING. SHEET A.06 DETAIL # 1
 INDICATES THE TOP OF THE COUNTER IS 34 INCHES HIGH.
 DISCREPANCY IN THE PLANS. THE 2020 FBC-ACCESSIBILITY
 CODE SECTION 902.3 HEIGHT. THE TOPS OF DINING SURFACES
 AND WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34
 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 1B) AT THE FRONT OF THE BUILDING BETWEEN THE 2 ENTRY
 DOORS THE FLOOR PLAN STATES CUSTOM FURNITURE BY OTHERS.
 SHEET A.06 SHOWS THE ELEVATION VIEW IN DETAIL # 2 WHICH
 APPEARS TO BE AN AREA CONSIDERED A HIGH-TOP WHERE THE
 MEAL OR DRINK CAN BE CONSUMED. PLEASE PROVIDE WHAT THE
 INTENT IS IN THIS AREA. WITH 6 SEATS THE ONE SEAT MEETS
 THE REQUIREMENT FOR THE ACCESSIBILITY CODE @ 0.05
 PERCENT. THE COUNTER IN QUESTION IS 10 FEET LONG. IF
 THE PATRONS ARE STANDING @ EVERY 18 INCHES THAT WOULD
 MAKE AN ADDITIONAL 7 PATRONS PLUS THE SEATED 6 EQUALS
 13. 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902. 13 X 0.05= 0.65 THE
 0.05 PERCENT ARE STILL MET BUT DISPERSION IS A ISSUE.
  
 1C) 2020 ACCESS. CODE 226.2 DISPERSION. DINING SURFACES
 AND WORK SURFACES REQUIRED TO COMPLY WITH 902 SHALL BE
 DISPERSED THROUGHOUT THE SPACE OR FACILITY CONTAINING
 DINING SURFACES AND WORK SURFACES.
  
 1D) THE OTHER UNKNOWN IS IF THERE WILL BE SEASONABLE
 SEATING ON THE EXTERIOR OF THE RESTAURANT. 2020
 FBC-ACCESS. CODE 206.2.5 206.2.5 RESTAURANTS AND
 CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 INCLUDING RAISED OR SUNKEN DINING AREAS, AND OUTDOOR
 DINING AREAS.
  
 1E) THE FLOOR PLAN INDICATES THE POINT OF SALE COUNTER
 TO BE 36 INCHES IN HEIGHT. CHECK WRITING SURFACES. 2017
 ACCESS. CODE 904.3.3 CHECK WRITING SURFACES. WHERE
 PROVIDED, CHECK WRITING SURFACES SHALL COMPLY WITH
 902.3HEIGHT. THE TOPS OF WORK SURFACES SHALL BE 28
 INCHES MINIMUM AND 34 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 SHOW COMPLIANCE WITH THE ACCESS. CODE 305.5 POSITION.
 UNLESS OTHERWISE SPECIFIED, CLEAR FLOOR OR GROUND SPACE
 SHALL BE POSITIONED FOR EITHER A FORWARD OR PARALLEL
 APPROACH TO AN ELEMENT.
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTERTOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTERTOP.
  
 1F) THE NEWLY EXPANDED UNISEX RESTROOM DOES NOT PROVIDE
 THE OVERALL WIDTH OF THE RESTROOM (BACK WALL) NOR DOES
 THE DETAIL 7/ A.07. THE 2020 FBC-B SECTION 604.3
 CLEARANCES.
 2) SHEET A.07:
 2) DETAILS 3 & 6 SHOW THE WATER CLOSET GRAB BARS BEING
 MEASURED FROM FINISH FLOOR TO THE CENTER LINE OF THE
 GRAB BAR. 2020 FBC-ACCESSIBILITY CODE SECTION 609.4
 POSITION OF GRAB BARS. GRAB BARS SHALL BE INSTALLED IN
 A HORIZONTAL POSITION, 33 INCHES MINIMUM AND 36 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE, NOT CENTERLINE.
  
 3A) SHEET S.02 & S.03 BOTH SHOW NEW STRUCTURAL STEEL
 ANGLE RE-ENFORCING BEING ADDED TO THE BAR JOIST AND
 ADDITIONAL STEEL REINFORCEMENT TO MAKE A STRUCTURAL
 FRAME FOR THE NEW RTU ON THE ROOF TOP. THIS BUILDING
 CONTAINS EITHER BOLTED AND OR WELDED CONNECTIONS. THE
 CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE
 SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION FOR FIELD WIELDING, ON
 THE JOB-SITE WIELDING. THIRD PARTY CERTIFICATION WILL
 BE REQUIRED.
 THE OWNER MAY JUST HIRE A 3RD PARTY ENGINEERING FIRM TO
 COMPLETE AND APPROVE THE FORMER INSPECTIONS. REPORTS
 SUBMITTED TO BUILDING INSPECTOR AT TIME OF FRAMING
 INSPECTION.
 2020 FBC-B 2204.1 WELDING
 1. WELD PROCEDURES SPECIFICATIONS
 2. QUALIFICATIONS OF WELDING PERSONAL
 2017 FBC-B 2204.2 BOLTING.
 IF FURTHER CLARIFICATION AND OR QUESTIONS IS REQUIRED,
 PLEASE CONTACT THE CHIEF BUILDING INSPECTOR
 KEN CONRAD AT 561-805-6666.
  
 3B) ROOF TOP CURBS. NO PRODUCT APPROVAL WAS SUBMITTED
 THIS REVIEW CYCLE. COMPONENTS & CLADDING. 2020 FBC-B
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF REPORT
 NOA, CURBS, ROOF TOP VENTILATORS.
  
 3C) W. P. B. 107.3.4. PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY FLORIDA ADMINISTRATIVE CODE RULE
 61G20 SHALL BE REVIEWED AND APPROVED IN WRITING (SHOP
 DRAWING STAMP OF APPROVAL) BY THE DESIGNER OF RECORD
 PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. FL
 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC.
  
 3D) SECTION 5 OF SHEET S.03 SHOWS THE ANCHORING OF THE
 CURB TO THE NEW ROOF TOP ANGLE IRON BUT THERE IS NO
 INFORMATION AS HOW THE NEW RTU IS GOING TO BE ANCHORED
 TO THE CURB. 2020 FBC-M- 301.15 WIND RESISTANCE.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
 FBC-B-1609.6.4.4.1 COMPONENTS AND CLADDING. WIND
 PRESSURE FOR EACH COMPONENT OR CLADDING ELEMENT IS TO
 BE DESIGNED FOR WIND PRESSURES COMPONENTS AND
 ATTACHMENTS.
  
 LATERAL FORCE-RESISTING SYSTEM. FOR ALL ROOF TOP
 EQUIPMENT, CURBS, FANS OR A/C STANDS, AND OR VENTS,
 DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL
 AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE.
  
 2020 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON STRUCTURAL
 MEMBERS AND THEIR CONNECTIONS SHALL BE DETERMINED BY
 METHODS OF STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT
 EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC COMPATIBILITY
 AND BOTH SHORT- AND LONG-TERM MATERIAL PROPERTIES.
 EVERY STRUCTURE SHALL BE DESIGNED TO RESIST THE
 OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES
 SPECIFIED IN THIS CHAPTER. SEE SECTION 1609 FOR WIND
 LOADS.
  
 4A) SHEET A.07 DETAIL 1 SHOWS TO THE BOTTOM OF THE
 STEEL ROOF DECK AN ELEVATION OF 14 FEET 4 INCHES AND
 WHAT APPEARS TO BE A PARAPET ABOVE THE ROOF. THIS
 INFORMATION IS NOT GIVEN. 2020 FBC-M 306.5 EQUIPMENT
 AND APPLIANCES ON ROOFS OR ELEVATED STRUCTURES. WHERE
 EQUIPMENT REQUIRING ACCESS OR APPLIANCES ARE LOCATED ON
 AN ELEVATED STRUCTURE OR THE ROOF OF A BUILDING SUCH
 THAT PERSONNEL WILL HAVE TO CLIMB HIGHER THAN 16 FEET
 (4877 MM) ABOVE GRADE TO ACCESS SUCH EQUIPMENT OR
 APPLIANCES, AN INTERIOR OR EXTERIOR MEANS OF ACCESS
 SHALL BE PROVIDED. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES (762
 MM) IN HEIGHT OR WALKING ON ROOFS HAVING A SLOPE
 GREATER THAN 4 UNITS VERTICAL IN 12 UNITS HORIZONTAL
 (33-PERCENT SLOPE). SUCH ACCESS SHALL NOT REQUIRE THE
 USE OF PORTABLE LADDERS. WHERE ACCESS INVOLVES CLIMBING
 OVER PARAPET WALLS, THE HEIGHT SHALL BE MEASURED TO THE
 TOP OF THE PARAPET WALL.
  
 4B) SHEET S.02 THE OTHER ISSUE WITH NOT KNOWING THE
 PARAPET HEIGHT IS COMPLIANCE WITH SECTION 2020 FBC-B
 1015.7 ROOF ACCESS GUARDS. GUARDS SHALL BE PROVIDED
 WHERE THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET
 OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE AND
 SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 INCHES
 ABOVE THE FLOOR, ROOF OR GRADE BELOW. THE GUARD SHALL
 BE CONSTRUCTED SO AS TO PREVENT THE PASSAGE OF A SPHERE
 21 INCHES (533 MM) IN DIAMETER.
  
 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID
 19
 IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS
 561-718-9724.
 WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/
 RETIRED.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  