2021-07-14 13:20:56 | WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION |
| SERVICES/ BUILDING DIVISION |
| 2020 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 21041226 |
| ADD: 5200 N. FLAGLER DR. # 1105 |
| CONT: J & M CONTRACTORS OF SOUTH FLORIDA, INC. |
| TEL: 561-433-3440 |
| E-MAIL: [email protected] |
| |
| 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION |
| |
| 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: WED. JULY 14TH/ 2021 |
| ACTION: DENIED |
| |
| 1) THE FLOOR PLAN INDICATES THE EXTERIOR BALCONY IS TO |
| BE TILED. THE CITY W. P. B. BUILDING DEPARTMENT WILL |
| NEED AN SIGNED & SEALED ENGINEER?S LETTER STATING THERE |
| ARE NO STRUCTURAL CRACKS IN THE BALCONY DECK, AND NO |
| SPAWLING OF CONCRETE ON THE BALCONY DECK (EXPOSED |
| RE-BAR, IF SO WHAT WILL BE NEEDED TO CORRECT THE ISSUES |
| AND SEAL THEM. IN ADDITION THE STRUCTURAL ENGINEER IS |
| TO VERIFY WITH AN ADDITIONAL LAYER OF TILE THE BALCONY |
| DECK THERE IS HEIGHT ENOUGH FOR THE SLIDING DOOR TRACKS |
| TO ALLOW THE WEEP WATER OUT OF THE TRACK AND OVER THE |
| NEW FLOOR TILE AND OVER THE EDGE OF THE BALCONY. |
| |
| 2) THE SUBMITTED FLOOR PLAN (DATED 4/28) INDICATED NEW |
| PORCELAIN FLOOR TILE ON THE BALCONY AND 2 BATHROOM |
| FLOORS. ALL CROSS-HATCHED AREAS WOOD FLOORING. THE |
| PROPOSED FLOOR PLAN (DATED 6/18) DOES NOT STATE TILE TO |
| BE INSTALLED ON THE EXTERIOR BALCONY. NO MENTION OF |
| TILE FLOORS IN THE MASTER BATH (NO FLOOR TILE WORK BATH |
| # 2), HARDWOOD FLOORS THROUGH-OUT THE REMAINDER OF THE |
| UNIT. PLEASE CLARIFY WILL THERE BE TILE ON THE BALCONY, |
| WITHIN THE BATHROOMS WILL TILE BE INSTALLED OR HARDWOOD |
| FLOORING. PLEASE ALSO SPECIFY WHEN STATING WOOD |
| FLOORING, IS THIS ? INCH HARWOOD FLOORING OR A LAMINATE |
| FLOORING, AND THE THICKNESS. 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 3) SUBMITTED IS A SALES BROCHURE FOR PROFLEX SUPER SIM |
| 90 FOR TILE. THERE WAS NO LITERATURE SUBMITTED FOR |
| EITHER ? INCH HARDWOOD FLOORING OR FOR LAMINATE |
| FLOORING. FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR |
| TYPE II BUILDINGS SHOWING COMPLIANCE WITH: |
| |
| 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492. |
| |
| 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 4) THE FLOOR PLAN INDICATES THE REMOVAL OF THE TUB AND |
| NEW SHOWER PLEASE SHOW COMPLIANCE WITH: |
| |
| 4A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS |
| IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO |
| BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR |
| SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION |
| CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 4B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE |
| FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE |
| WITH THE 2020 FBC-B SECTION 714.5.1.2. |
| THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL |
| ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY |
| A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN |
| ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL |
| HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT |
| NOT LESS THAN THE REQUIRED RATING OF THE FLOOR |
| PENETRATED. |
| |
| 4C) 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS |
| A BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS |
| AND CEILING PANELS IN SHOWER AREAS SHALL BE OF |
| MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN |
| ACCORDANCE WITH MANUFACTURER?S RECOMMENDATIONS. WATER |
| RESISTANT GYPSUM BACKING BOARD SHALL BE USED AS A BASE |
| FOR TILE IN WATER CLOSET COMPARTMENT WALLS WHEN |
| INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM C840 AND |
| THE MANUFACTURE?S RECOMMENDATIONS. |
| |
| 4D) 2020 FBC-B SHOWERS & TUBS 1210.3. SHOWER |
| COMPARTMENTS AND BATHTUBS WITH INSTALLED SHOWER HEADS |
| SHALL BE FINISHED WITH A NONABSORBENT SURFACE TO A |
| HEIGHT NOT LESS THAN 72 INCHES ABOVE THE DRAIN INLET. |
| |
| 5) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS |
| REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT |
| REVIEW CYCLE. |
| |
| PLEASE NOTE WE ARE WORKING FROM HOME BECAUSE OF COVID |
| 19 |
| IF YOU WOULD LIKE TO CONTACT ME, MY CELL NUMBER IS |
| 561-718-9724. |
| WORKING HOURS ARE MON.- WED. 8:00 AM- NOON. PART-TIME/ |
| RETIRED. |
| |