Plan Review Notes For Permit 21041147 |
Permit Number |
21041147 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-28 10:30:49 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) SUBMIT A GENERATOR PAD DRAWING THAT SPECIFIES HOW | | THE GENERATOR IS ANCHORED TO RESIST WIND LOADS. IF YOU | | ARE USING A PREFABRICATED GENERATOR PAD SUBMIT THE | | SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR IT. | | SPECIFY THE WIND LOAD DATA ON THE DRAWING. FBC 107.2.1 | | | | 2) SEE SIGNATURE REVIEW. |
|