2021-08-20 17:27:44 | NEW DUPLEX (R3) SECOND BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21041108 |
| |
| NOTE: |
| BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR |
| TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME |
| OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT |
| ISSUANCE. |
| |
| ***NOTE: PLANS NEED ARCHITECT'S SIGNATURE BEFORE |
| APPROVING WITH PROVISO. SEE ITEM #1 BELOW. |
| |
| 1- ARCHITECTURAL AND STRUCTURAL PLANS SUBMITTED DON'T |
| HAVE THE ARCHITECT'S SEAL AND SIGNATURE. ALL DRAWINGS |
| NEED ARCHITECT'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY |
| SEC. 481 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC |
| RECORDS. |
| PLANS WERE SUBMITTED ELECTRONICALLY. NEED PLANS WITH |
| ARCHITECT'S DIGITAL SIGNATURE OR PROVIDE HARD COPY |
| PLANS WITH THE ORIGINAL SEAL AND SIGNATURE. |
| |
| 2- PROVIDE DETAIL AND SPECIFICATIONS FOR MONOLITHIC |
| BEAM SUPPORTING THE 7" CONCRETE SLAB SHOWN ON THE TWO |
| STORY WALL SECTION AND BUILDING SECTION A-A. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 3- ENERGY CALCULATIONS (FIRST FLOOR): |
| A)ITEM #2 IS INCORRECT. ITEM #2 IS ASKING IF "SINGLE |
| FAMILY OR MULTIPLE FAMILY". WHAT IS "ATTACHED". REVISE |
| AS REQUIRED. PROVIDE CORRECT ANSWER. |
| NOTE: REVISE ITEM #3 ALSO. PROVIDE NUMBER OF UNITS. |
| THIS IS A DUPLEX. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| B)ITEM #5 SPECIFIES NO WORST CASE SCENARIO, BUT TOP OF |
| PAGE 2 SPECIFIES AN ANGLE ROTATION OF 270 DEGREES. |
| REVISE AS REQUIRED. ENERGY CALCULATIONS NEED TO BE SITE |
| SPECIFIC AS REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY |
| CONSERVATION. |
| |
| C)CEILING INFORMATION ON ITEM #11 IS INCORRECT. REVISE |
| THE AREA. THE CEILING OF THE FIRST FLOOR IS THE SECOND |
| FLOOR ASSEMBLY AND IT IS NOT VENTED. ALSO, |
| ARCHITECTURAL PLANS DON'T SPECIFY INSULATION. REVISE AS |
| REQUIRED TO MATCH PLANS. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| D)CEILING INFORMATION ON PAGE 3 OF 6 IS INCORRECT. THE |
| CEILING ON FIRST FLOOR IS NOT WOOD. SEE PLANS AND |
| REVISE AS REQUIRED. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| E)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT. |
| ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY |
| DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR |
| SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS |
| REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION. |
| REVISE AS REQUIRED. |
| |
| F) WINDOWS INFORMATION ON PAGE 4 OF 6 DOESN'T MATCH |
| PLANS. REVISE WINDOW ORIENTATION, WINDOW AREA AND |
| WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH |
| ARCHITECT'S PLANS AND EXTERIOR ELEVATIONS. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| G)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| 5- ENERGY CALCULATIONS (SECOND FLOOR): |
| A)ITEM #2 IS INCORRECT. IT IS ASKING IF "SINGLE FAMILY |
| OR MULTIPLE FAMILY". WHAT IS "ATTACHED". REVISE AS |
| REQUIRED. PROVIDE CORRECT ANSWER. |
| NOTE: REVISE ITEM #3 ALSO. PROVIDE NUMBER OF UNITS. |
| THIS IS A DUPLEX. |
| SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION. |
| |
| B)ITEM #5 SPECIFIES NO WORST CASE SCENARIO, BUT TOP OF |
| PAGE 2 SPECIFIES AN ANGLE ROTATION OF 270 DEGREES. |
| REVISE AS REQUIRED. ENERGY CALCULATIONS NEED TO BE SITE |
| SPECIFIC AS REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY |
| CONSERVATION. |
| |
| C)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT. |
| ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY |
| DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR |
| SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS |
| REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION. |
| REVISE AS REQUIRED. |
| |
| D)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY |
| CONSERVATION. |
| |
| 3- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVALS PRIOR |
| TO INSTALLATION. ALL PRODUCT APPROVALS NEED TO BE |
| APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO |
| SUBMITTAL: |
| A)ENTRY DOOR. |
| B)SLIDING GLASS DOORS. |
| C)SINGLE HUNG WINDOWS |
| D)ROOF SHINGLES. |
| E)ROOF RIDGE VENT. SEE ROOF RIDGE DETAIL ON SHEET A-5. |
| F)SHUTTERS WITH COMPLETE INSTALLATION SCHEDULE IF DOORS |
| AND WINDOWS DON'T HAVE IMPACT GLAZING. |
| |
| 4- WINDOWS AND DOORS DETAILS ON SHEET A-4 ARE MISSING |
| THE STRUCTURAL BUCK FASTENING SPECIFICATIONS. DESIGNER |
| OF RECORD NEEDS TO SPECIFY FASTENER TYPE, SIZE AND |
| SPACING. PRODUCT APPROVAL IS ONLY FOR THE WINDOW/DOOR |
| ATTACHMENT. |
| SEC. R301.1 FBC-RESIDENTIAL. |
| |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |