Plan Review Notes
Plan Review Notes For Permit 21041108
Permit Number 21041108
Review Stop B
Sequence Number 2
Notes
Date Text
2021-08-20 17:27:44NEW DUPLEX (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21041108
  
 NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY. CONTRACTOR
 TO ADVICE IF PROVISO OPTION IS PREFERRED AT THIS TIME
 OR IF RE-SUBMITTING REQUIRED INFORMATION BEFORE PERMIT
 ISSUANCE.
  
 ***NOTE: PLANS NEED ARCHITECT'S SIGNATURE BEFORE
 APPROVING WITH PROVISO. SEE ITEM #1 BELOW.
  
 1- ARCHITECTURAL AND STRUCTURAL PLANS SUBMITTED DON'T
 HAVE THE ARCHITECT'S SEAL AND SIGNATURE. ALL DRAWINGS
 NEED ARCHITECT'S ORIGINAL SEAL/SIGNATURE AS REQUIRED BY
 SEC. 481 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC
 RECORDS.
 PLANS WERE SUBMITTED ELECTRONICALLY. NEED PLANS WITH
 ARCHITECT'S DIGITAL SIGNATURE OR PROVIDE HARD COPY
 PLANS WITH THE ORIGINAL SEAL AND SIGNATURE.
  
 2- PROVIDE DETAIL AND SPECIFICATIONS FOR MONOLITHIC
 BEAM SUPPORTING THE 7" CONCRETE SLAB SHOWN ON THE TWO
 STORY WALL SECTION AND BUILDING SECTION A-A.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- ENERGY CALCULATIONS (FIRST FLOOR):
 A)ITEM #2 IS INCORRECT. ITEM #2 IS ASKING IF "SINGLE
 FAMILY OR MULTIPLE FAMILY". WHAT IS "ATTACHED". REVISE
 AS REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: REVISE ITEM #3 ALSO. PROVIDE NUMBER OF UNITS.
 THIS IS A DUPLEX.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B)ITEM #5 SPECIFIES NO WORST CASE SCENARIO, BUT TOP OF
 PAGE 2 SPECIFIES AN ANGLE ROTATION OF 270 DEGREES.
 REVISE AS REQUIRED. ENERGY CALCULATIONS NEED TO BE SITE
 SPECIFIC AS REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION.
  
 C)CEILING INFORMATION ON ITEM #11 IS INCORRECT. REVISE
 THE AREA. THE CEILING OF THE FIRST FLOOR IS THE SECOND
 FLOOR ASSEMBLY AND IT IS NOT VENTED. ALSO,
 ARCHITECTURAL PLANS DON'T SPECIFY INSULATION. REVISE AS
 REQUIRED TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)CEILING INFORMATION ON PAGE 3 OF 6 IS INCORRECT. THE
 CEILING ON FIRST FLOOR IS NOT WOOD. SEE PLANS AND
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 F) WINDOWS INFORMATION ON PAGE 4 OF 6 DOESN'T MATCH
 PLANS. REVISE WINDOW ORIENTATION, WINDOW AREA AND
 WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH
 ARCHITECT'S PLANS AND EXTERIOR ELEVATIONS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 G)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 5- ENERGY CALCULATIONS (SECOND FLOOR):
 A)ITEM #2 IS INCORRECT. IT IS ASKING IF "SINGLE FAMILY
 OR MULTIPLE FAMILY". WHAT IS "ATTACHED". REVISE AS
 REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: REVISE ITEM #3 ALSO. PROVIDE NUMBER OF UNITS.
 THIS IS A DUPLEX.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 B)ITEM #5 SPECIFIES NO WORST CASE SCENARIO, BUT TOP OF
 PAGE 2 SPECIFIES AN ANGLE ROTATION OF 270 DEGREES.
 REVISE AS REQUIRED. ENERGY CALCULATIONS NEED TO BE SITE
 SPECIFIC AS REQUIRED BY SEC. R405.4.2.1 (4) FBC- ENERGY
 CONSERVATION.
  
 C)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 D)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 3- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVALS PRIOR
 TO INSTALLATION. ALL PRODUCT APPROVALS NEED TO BE
 APPROVED IN WRITING BY DESIGNER OF RECORD PRIOR TO
 SUBMITTAL:
 A)ENTRY DOOR.
 B)SLIDING GLASS DOORS.
 C)SINGLE HUNG WINDOWS
 D)ROOF SHINGLES.
 E)ROOF RIDGE VENT. SEE ROOF RIDGE DETAIL ON SHEET A-5.
 F)SHUTTERS WITH COMPLETE INSTALLATION SCHEDULE IF DOORS
 AND WINDOWS DON'T HAVE IMPACT GLAZING.
  
 4- WINDOWS AND DOORS DETAILS ON SHEET A-4 ARE MISSING
 THE STRUCTURAL BUCK FASTENING SPECIFICATIONS. DESIGNER
 OF RECORD NEEDS TO SPECIFY FASTENER TYPE, SIZE AND
 SPACING. PRODUCT APPROVAL IS ONLY FOR THE WINDOW/DOOR
 ATTACHMENT.
 SEC. R301.1 FBC-RESIDENTIAL.
  
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]