2021-05-18 23:36:49 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NO EQUIPMENT GROUND SHOWN FROM SERVICE DISCONNECTS |
| TO INTERIOR PANELS. NEC 250.4A3 |
| |
| 2. RISER ONLY SHOWS ONE METER AND DISC BUT PLANS SHOWS |
| DISC/METER FOR EACH UNIT. PROVIDE CORRECTION. FBC |
| 107.2.1 |
| |
| 3. FOR A ONE FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE LEVEL, AT LEAST |
| ONE RECEPTACLE OUTLET READILY ACCESSIBLE FROM GRADE AND |
| NOT MORE THAN 2.0 M (6.5 FT) ABOVE GRADE LEVEL SHALL BE |
| INSTALLED AT THE FRONT AND BACK OF THE DWELLING. |
| PROVIDE CORRECTION. NEC 210.52(E)(1) FBC RE E3901.7 |
| |
| 4. NO ARC-FAULT PROTECTION SHOWN. PROVIDE CORRECTION |
| PER NEC 210.12 |
| |
| 5. SMOKE ALARMS MUST BE 3FT FROM BEDROOMS NFPA 72 |
| 29.8.3.4 #6 |
| |
| 6. NO WORKING CLEARANCE FOR AC CONDENSOR DISCONNECTS |
| NEC 110.26A1 |
| |
| 7. TAMPERPROOF RECEPTACLES REQUIRED NEC 406.12 |
| |
| 8. GEC TO CONCRETE ENCASED ELECTRODE IS TO BE MINIMUM |
| #4 CU NEC 250.66B |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |