Plan Review Notes For Permit 21041108
Permit Number 21041108
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-16 14:08:37COMMENTS UPDATED 07/07/21 AND EMAILED TO VICTOR
 VELASQUEZ.
 THERE IS A CONCERN ABOUT THE DESIGN OF THE BEAM AND
 COLUMNS SUPPORTING THE WEIGHT OF PROPOSED 8" CONCRETE
 SLAB (THIS WAS DISCUSSED WITH ROBERT BROWN, BUILDING
 OFFICIAL):
 1- SECOND FLOOR CONCRETE SLAB:
 A)STRUCTURAL PLANS SHOW AN 8" CONCRETE SLAB TO BE
 SUPPORTED ON 8X20 CONCRETE BEAM AND 3-1/4 X 3-1/4 X 1/4
 TUBE COLUMNS. PROVIDE CALCULATIONS SHOWING THAT THE
 STEEL REINFORCEMENT SPECIFIED FOR THE CONCRETE BEAM
 (2#5 BARS ON TOP AND 2#7 BARS AT BOTTOM)IS ADEQUATE TO
 TRANSFER THE BENDING MOMENT OF THE CONTINUOUS CONCRETE
 BEAM AT THE STEEL COLUMNS. ALSO, CHECK THE BUCKLING OF
 THE TUBE COLUMNS. SEC. 107.2.1.2 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
 B)FOUNDATION PLAN IS MISSING THE FOOTING FOR COLUMN
 SUPPORTING THE REAR END OF 8X20 CONCRETE BEAM. SEC.
 107.2.1.2 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
 C)CLARIFY WHY COLUMN SUPPORTING THE REAR END OF 8X20
 CONCRETE BEAM IS DIFFERENT THAN THE ONE SPECIFIED AT
 THE FRONT END. SEC. 107.2.1.2 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
  
  
  
 COMMENTS UPDATED 06/22/21.
 GOOD AFTERNOON MR. VELASQUEZ,
 THE ANSWER IS YES. YOU NEED TO PROVIDE AN APPROVED
 ASSEMBLY THAT MEETS THE FIRE RATING SPECIFIED ON THE
 TWO STORY WALL SECTION AND BUILDING SECTION A-A.
 THE ASSEMBLY NEEDS TO BE TESTED IN ACCORDANCE WITH ASTM
 E119 OR UL 263 OR ANY OTHER METHOD DESCRIBED IN SEC.
 703.3 FBC-BUILDING.
  
 NOTE:
 1) ALSO, NEED TO PROVIDE A FIRE RATED WALL ASSEMBLY FOR
 FIRST FLOOR EXTERIOR WALL SUPPORTING THE SECOND FLOOR
 ASSEMBLY SPECIFIED ON TWO STORY WALL SECTION AND
 BUILDING SECTION A-A.
 I APOLOGIZE, I MEANT TO ADD THIS IN MY COMMENTS, BUT
 SOMEHOW I DIDN'T DO IT. NOW THAT I HAVE A SECOND CHANCE
 TO READ THE COMMENTS I REALIZED THIS. I WILL UPDATE MY
 COMMENTS ACCORDINGLY.
  
 2)ALSO, PROVIDE DETAIL AND SPECIFICATIONS FOR
 MONOLITHIC BEAM SUPPORTING THE 8" CONCRETE SLAB SHOWN
 ON THE TWO STORY WALL SECTION AND BUILDING SECTION A-A.
 I APOLOGIZE, I MEANT TO ADD THIS IN MY COMMENTS, BUT
 SOMEHOW I DIDN'T DO IT. NOW THAT I HAVE A SECOND CHANCE
 TO READ THE COMMENTS I REALIZED THIS. I WILL UPDATE MY
 COMMENTS ACCORDINGLY.
  
 THANK YOU
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  
  
 NEW DUPLEX (R3) BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21041108
  
 1- INTERIOR STEEL COLUMNS SUPPORTING THE SECOND FLOOR
 CONCRETE SLAB NEED TO BE FIRE RATED AS REQUIRED BY SEC.
 R302.3.1 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR APPROVED ASSEMBLIES SHOWING FIRE
 RESISTANCE COMPLIANCE.
  
 2- SECOND FLOOR ASSEMBLY: PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS FOR APPROVED ASSEMBLIES SHOWING FIRE
 RESISTANCE COMPLIANCE THRU FLOOR ASSEMBLY PENETRATIONS
 AS REQUIRED BY SEC. 302.4 FBC-RESIDENTIAL.
  
 3- LOT DRAINAGE:
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 4- ENERGY CALCULATIONS (FIRST FLOOR):
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)DESIGN LOCATION SPECIFIED ON TOP OF FORM 405-2020 AND
 UNDER CLIMATE HEADING ON PAGE 2 OF 6 IS INCORRECT. THIS
 HOUSE IS NOT IN FORT PIERCE. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED CORRECT LOCATION AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)ITEM #2 IS NOT CLEAR. ITEM #2 IS ASKING IF "SINGLE
 FAMILY OR MULTIPLE FAMILY". WHAT IS "DETACHED". REVISE
 AS REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: COORDINATE WITH ITEM #3.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)ITEM #5 SPECIFIES WORST CASE SCENARIO. ENERGY
 CALCULATIONS NEED TO BE SITE SPECIFIC AS REQUIRED BY
 SEC. R405.4.2.1 (4) FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA SPECIFIED ON ITEM #6 DOESN'T
 MATCH AREA SPECIFIED ON ARCHITECT'S PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)CEILING INFORMATION ON ITEM #11 IS INCORRECT. REVISE
 THE AREA. THE CEILING OF THE FIRST FLOOR IS THE SECOND
 FLOOR ASSEMBLY AND IT IS NOT VENTED. ALSO,
 ARCHITECTURAL PLANS DON'T SPECIFY INSULATION. REVISE AS
 REQUIRED TO MATCH PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)ROOF INFORMATION ON PAGE 3 OF 6 IS INCORRECT. REVISE
 AS REQUIRED.
 NOTE: COORDINATE WITH ITEM 4(G) ABOVE. AND, COORDINATE
 WITH ARCHITECT'S PLANS FOR SECOND FLOOR ENERGY
 CALCULATIONS. SEE CORRECT ROOF TYPE AND ROOFING
 MATERIAL.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 I)ATTIC INFORMATION ON PAGE 3 OF 6 IS INCORRECT. THERE
 IS NOT ATTIC ON THE FIRST FLOOR.
 NOTE: COORDINATE WITH ITEM 4(G) ABOVE. AND, COORDINATE
 WITH ARCHITECT'S PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 J)CEILING INFORMATION ON PAGE 3 OF 6 IS INCORRECT. THE
 CEILING ON FIRST FLOOR IS CONCRETE NOT WOOD. SEE PLANS.
 NOTE: COORDINATE WITH ITEM 4(G) ABOVE. AND, COORDINATE
 WITH ARCHITECT'S PLANS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 K)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 L) WINDOWS INFORMATION ON PAGE 4 OF 6 DOESN'T MATCH
 PLANS. REVISE WINDOW ORIENTATION, WINDOW AREA AND
 WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH
 ARCHITECT'S PLANS AND EXTERIOR ELEVATIONS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 M)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 5- ENERGY CALCULATIONS (SECOND FLOOR):
 A)THE ENERGY FORM R405-2020 IS REQUIRED TO BE SIGNED
 AND DATED BY THE OWNER, ARCHITECT OR OWNER?S LEGALLY
 DESIGNATED AGENT AT THE BOTTOM OF FORM SUBMITTED AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 PRIOR TO RECEIVING THE PERMIT TO BEGIN CONSTRUCTION.
  
 B)DESIGN LOCATION SPECIFIED ON TOP OF FORM 405-2020 AND
 UNDER CLIMATE HEADING ON PAGE 2 OF 6 IS INCORRECT. THIS
 HOUSE IS NOT IN FORT PIERCE. REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. NEED CORRECT LOCATION AND BUILDER'S NAME. SEC.
 R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 D)ITEM #2 IS NOT CLEAR. ITEM #2 IS ASKING IF "SINGLE
 FAMILY OR MULTIPLE FAMILY". WHAT IS "DETACHED". REVISE
 AS REQUIRED. PROVIDE CORRECT ANSWER.
 NOTE: COORDINATE WITH ITEM #3.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 E)ITEM #5 SPECIFIES WORST CASE SCENARIO. ENERGY
 CALCULATIONS NEED TO BE SITE SPECIFIC AS REQUIRED BY
 SEC. R405.4.2.1 (4) FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 F)CONDITIONED FLOOR AREA SPECIFIED ON ITEM #6 DOESN'T
 MATCH AREA SPECIFIED ON ARCHITECT'S PLANS. REVISE AS
 REQUIRED TO MATCH.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 G)CEILING INFORMATION ON ITEM #11 IS INCORRECT. REVISE
 THE CEILING AREA.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 H)ROOF INFORMATION ON PAGE 3 OF 6 IS INCORRECT. TYPE OF
 ROOF IS NOT GABLE. THE ROOFING MATERIAL IS NOT BARREL
 TILE. SEE PLANS AND REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 I)ATTIC INFORMATION ON PAGE 3 OF 6 IS INCORRECT.
 TYPICALLY VENT RATIO IS 1/150. SEE SEC. R806.2
 FBC-RESIDENTIAL. SEE PLANS AND REVISE AS REQUIRED.
 (PLANS DON'T SHOW VENTILATION RATIO OF 1/300 AS ALLOWED
 BY THE EXCEPTION OF SEC. R806.2 FBC-RESIDENTIAL).
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 J)DOORS INFORMATION ON PAGE 4 OF 6 IS INCORRECT.
 ACCORDING TO ARCHITECT'S EXTERIOR ELEVATIONS, ENTRY
 DOORS HAVE A LARGE GLASS PANEL. SEE PLANS. THIS DOOR
 SHOULD BE INCLUDED IN THE WINDOW/GLAZING AREA AS
 REQUIRED BY SEC. R405.5.3 FBC- ENERGY CONSERVATION.
 REVISE AS REQUIRED.
  
 K) WINDOWS INFORMATION ON PAGE 4 OF 6 DOESN'T MATCH
 PLANS. REVISE WINDOW ORIENTATION, WINDOW AREA AND
 WINDOW OVERHANG DEPTH AND SEPARATION TO MATCH
 ARCHITECT'S PLANS AND EXTERIOR ELEVATIONS.
 SEC. R101.5.1.1.2 FBC- ENERGY CONSERVATION.
  
 L)BUILDER TO COMPLETE AND SIGN THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC-ENERGY
 CONSERVATION.
  
 6- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 HANDRAILS AND GUARDRAILS SHOWING COMPLIANCE TABLE
 R301.5, SEC. R311.7.8 AND SEC. R312.1 FBC-RESIDENTIAL.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION PRIOR TO
 INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL PRODUCT
 APPROVALS NEED TO BE APPROVED IN WRITING BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL):
  
 A)ENTRY DOOR.
 B)SLIDING GLASS DOORS.
 C)SINGLE HUNG WINDOWS
 D)ROOF SHINGLES.
 E)ROOF RIDGE VENT. SEE ROOF RIDGE DETAIL ON SHEET A-5.
 F)SHUTTERS WITH COMPLETE INSTALLATION SCHEDULE IF DOORS
 AND WINDOWS DON'T HAVE IMPACT GLAZING.
  
 8- PROVIDE DETAIL/SPECIFICATIONS FOR SECOND FLOOR
 FINISH FLOOR. NEED FLOOR SOUND INSULATION BETWEEN
 DWELLING UNITS AS REQUIRED BY SEC. 105.2 CITY
 AMENDMENTS.
 THE FOLLOWING FLOOR SOUND INFORMATION MAY BE SUBMITTED
 LATER AS A DEFERRED SUBMITTAL WHEN REVIEWED BY THE
 ARCHITECT OF RECORD:
 FLOORING SOUND INSULATION MATERIAL:
 A) PROVIDE COPY OF THE FLAME SPREAD INDEX AND SMOKE
 DEVELOPED INDEX TEST DONE IN ACCORDANCE WITH ASTM E 84
 OR UL 723 AS REQUIRED BY SEC. 720.1 OF FBC 7TH EDITION
 (2020).
 B) PROVIDE COPY OF THE SOUND TRANSMISSION CLASS (STC)
 TEST DONE IN ACCORDANCE WITH ASTM E 90 AS REQUIRED BY
 SEC. 1207.2 OF FBC 7TH EDITION (2020).
 C) PROVIDE COPY OF THE IMPACT INSULATION CLASS (IIC)
 TEST DONE IN ACCORDANCE WITH ASTM E 492 AS REQUIRED BY
 SEC. 1207.3 OF FBC 7TH EDITION (2020).
  
 9- WINDOWS AND DOORS DETAILS ON SHEET A-4 ARE MISSING
 THE STRUCTURAL BUCK FASTENING SPECIFICATIONS. DESIGNER
 OF RECORD NEEDS TO SPECIFY FASTENER TYPE, SIZE AND
 SPACING.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY
 AMENDMENTS. VALUATION WAS UPDATED TO $359,252. THE
 PERMIT FEE BALANCE IS $1825.90.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  