Date |
Text |
2021-11-01 15:00:04 | NEW SINGLE FAMILY RESIDENCE (R3) FOURTH BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #21041104 (MAIN HOUSE) |
| |
| 1- OK |
| 2- OK |
| 3- OK |
| 4- OK |
| 5- OK |
| |
| 6- REVISE ENERGY CALCULATIONS SUBMITTED: |
| |
| A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED |
| AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S |
| ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY |
| THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY |
| SEC. R103.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. |
| |
| B)OK |
| |
| C) DOOR ORIENTATION INFORMATION ON PAGE 3 OF 4 IS |
| INCORRECT. |
| SEE SURVEY/SITE PLAN AND FLOOR PLAN FOR CORRECT DOOR |
| ORIENTATION AND REVISE AS REQUIRED. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. |
| |
| D)WINDOWS INFORMATION ON PAGE 3 OF 4 DOESN'T MATCH |
| PLANS. |
| SEE SURVEY, FLOOR PLAN AND REVISE WINDOW ORIENTATION |
| AND AREA TO MATCH PLANS. |
| SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. |
| |
| E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE |
| LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY |
| CONSERVATION. |
| |
| RESPONSE: |
| REPEAT COMMENT. |
| |
| 7- OK |
| 8- OK |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| ANTICIPATED COOPERATION. |
| |
| PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| QUESTIONS REGARDING THESE COMMENTS, |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |
| |