2021-09-16 17:44:41NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21041104 (MAIN HOUSE)
  
 1- OK
  
 2- ADDRESS AND PARCEL CONTROL NUMBER (PCN) SHOWN ON ALL
 PLANS SUBMITTED IS INCORRECT. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NEED TO REVISE THE PARCEL CONTROL NUMBER (PCN) AND THE
 ADDRESS IN ALL DRAWINGS.
 NOTE: ASSIGNED ADDRESS FOR THE MAIN HOUSE IS 1132 11TH
 ST. REVISE ALL DRAWINGS AS REQUIRED.
  
 3- OK
  
 4- SHEET 4-4:
 REVISE/CLARIFY THE ROOF SHEATHING NOTE NEXT TO THE ROOF
 PLAN UNDER THE COMPONENT AND CLADDING PRESSURE ZONES
 TABLE. THIS NOTE CONTRADICTS THE NAIL SPACING
 SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING
 PRESSURE ZONES TABLE. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 RESPONSE:
 NOT ADDRESSED.
  
 5- OK
  
 6- REVISE ENERGY CALCULATIONS SUBMITTED:
  
 RESPONSE:
 ENERGY CALCULATIONS WERE NOT REVISED. NEED ENERGY
 CALCULATIONS FOR THE MAIN HOUSE. REVIEW COULD NOT BE
 DONE. SUBMIT ENERGY CALCULATIONS FOR THE MAIN HOUSE AND
 COORDINATE WITH ORIGINAL COMMENTS BELOW TO AVOID
 CONFLICTS/DELAYS.
  
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. PROVIDE CORRECT ADDRESS AND OWNER'S NAME, PROVIDE
 NAME OF BUILDER, PERMITTING OFFICE AND JURISDICTION
 NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT.
 (COORDINATE WITH ITEM #1 ABOVE).
 THIS BUILDING IS FACING CARVER AVE. THESE DOORS ARE
 LOCATED IN THE FRONT AND REAR OF BUILDING. SEE
 SURVEY/SITE PLAN AND FLOOR PLAN AND REVISE AS REQUIRED.
 . THEREFORE, THE CORRECT ORIENTATION IS WEST AND EAST.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCORRECT.
 (COORDINATE WITH ITEM #1 ABOVE).
 THIS BUILDING IS FACING CARVER AVE. SEE SURVEY/SITE
 PLAN AND FLOOR PLAN AND REVISE AS REQUIRED. THERE ARE
 NO WINDOWS ON THE SOUTH SIDE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 NEW COMMENTS:
 (NOTE: THIS IS THE FIRST REVIEW ON THE PLANS FOR THE
 MAIN HOUSE. THE FIRST REVIEW WAS BASED ONLY ON PLANS
 SUBMITTED FOR THE MOTHER-IN-LAW HOUSE).
  
 7- CLEARLY SPECIFY SIZE OF SINGLE HUNG EGRESS BEDROOM
 WINDOWS (WIDTH AND HEIGHT) AS SPECIFIED ON THE
 MOTHER-IN-LAW HOUSE PLANS. PLANS ONLY SPECIFY 25SH
 EGRESS BUT NO SIZE. SEC. R310.2.1 FBC-RESIDENTIAL.
  
 8- MISSING THE SHINGLES PRODUCT APPROVAL. PLEASE
 RESUBMIT. PRODUCT APPROVAL TO BE REVIEWED BY THE
 ENGINEER OF RECORD.
 SEC. 107.34.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION