Plan Review Notes
Plan Review Notes For Permit 21041103
Permit Number 21041103
Review Stop B
Sequence Number 3
Notes
Date Text
2021-09-17 13:58:23NEW SINGLE FAMILY RESIDENCE (R3) THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21041103
  
 1- OK
  
 2- OK
  
 3- OK
  
 4- SHEET 4-4:
 REVISE/CLARIFY THE ROOF SHEATHING NOTE NEXT TO THE ROOF
 PLAN UNDER THE COMPONENT AND CLADDING PRESSURE ZONES
 TABLE. THIS NOTE CONTRADICTS THE NAIL SPACING
 SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING
 PRESSURE ZONES TABLE. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 5- OK
  
 6- REVISE ENERGY CALCULATIONS SUBMITTED:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. PROVIDE CORRECT OWNER'S NAME, PROVIDE NAME OF
 BUILDER, PERMITTING OFFICE AND JURISDICTION NUMBER
 (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 C)WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCOMPLETE.
 MISSING THE MASTER BEDROOM WINDOW. SEC. R101.5.1.1.2
 FBC-ENERGY CONSERVATION.
  
 D)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. NOT ADDRESSED.
  
 NEW COMMENTS:
 (NOTE: THIS IS THE FIRST REVIEW ON THE PLANS FOR THE
 MAIN HOUSE. THE FIRST REVIEW WAS BASED ONLY ON PLANS
 SUBMITTED FOR THE MOTHER-IN-LAW HOUSE).
  
 7- CLEARLY SPECIFY SIZE OF SINGLE HUNG EGRESS BEDROOM
 WINDOWS (WIDTH AND HEIGHT) AS SPECIFIED ON THE
 MOTHER-IN-LAW HOUSE PLANS. PLANS ONLY SPECIFY 25SH
 EGRESS BUT NO SIZE. SEC. R310.2.1 FBC-RESIDENTIAL.
  
 NOTE:
 A)LANDSCAPE UNDER A SEPARATE PERMIT. PLANS WERE
 DELETED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,