Plan Review Notes
Plan Review Notes For Permit 21041103
Permit Number 21041103
Review Stop B
Sequence Number 2
Notes
Date Text
2021-08-10 15:47:3408/10/21 TALKED TO CARLOS RAMIREZ. THERE ARE TWO
 BUILDINGS PROPOSED IN THIS PARCEL. A PERMIT APPLICATION
 IS REQUIRED FOR EACH BUILDING. ONLY THE PLANS FOR THE
 REAR BUILDING WERE SUBMITTED FOR THE FIRST REVIEW.
 PLANS REVIEWERS WHO PASSED THE REVIEW STOP THE FIRST
 TIME MAY NOT BE AWARE OF THE TWO STRUCTURES. (TALKED TO
 ROBERT BROWN). TO AVOID MORE CONFUSION, I TOLD CARLOS
 RAMIREZ TO UPLOAD A SEPARATE PERMIT APPLICATION AND
 PLANS/SUPPORTING DOCUMENTS FOR EACH STRUCTURE.
 REVIEWS/COMMENTS WILL BE DONE UNDER EACH PERMIT NUMBER.
 JG.
  
  
  
 NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21041103
  
 1- FLOOR PLAN VIEW ON SHEET 1-3 SHOWS THE ENTRANCE OF
 THE BUILDING FACING NORTH. BASED ON THE AERIAL VIEW,
 THE STREET IS ON THE SOUTH SIDE NOT ON THE NORTH SIDE.
 THERE IS AN ALLEY ON THE NORTH SIDE OF THE LOT. IT
 LOOKS LIKE THE ORIENTATION OF THE BUILDING NEEDS TO BE
 REVISED.
 TYPICALLY, THE ADDRESS OF THE BUILDING IS BASED ON THE
 ENTRANCE LOCATION. COORDINATE WITH THE ADDRESSING
 COMMENTS FROM CAROLINE PUELL. THERE IS NO SURVEY OR
 SITE PLAN SUBMITTED. THEREFORE, THE PROPOSED
 ORIENTATION OF THE BUILDING ON THE LOT IS UNKNOWN.
 THE ORIENTATION OF THIS BUILDING AND THE EXTERIOR
 ELEVATIONS LABELING ON SHEET 1-3 MAY NEED TO BE
 REVISED. (NOTE: THIS IS AFFECTING THE ENERGY
 CALCULATIONS. THEY NEED TO BE COORDINATED WITH THE
 PROPOSED ORIENTATION. THIS IS WHY CORRECT ORIENTATION
 IS IMPORTANT).
 SEC. 107.2.1 CITY AMENDMENTS.
  
 2- ADDRESS SHOWN ON ALL PLANS SUBMITTED MAY NEED TO BE
 REVISED. COORDINATE WITH ITEM #1 ABOVE.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROVIDE SITE PLAN SHOWING THE PROPOSED BUILDING
 SETBACKS DRAWN IN ACCORDANCE WITH AN ACCURATE AND
 INCLUDED ON A BOUNDARY LINE SURVEY.
 SEC. 107.2.5 CITY AMENDMENTS.
  
 4- SHEET 3-3:
 REVISE/CLARIFY THE ROOF SHEATHING NOTE NEXT TO THE ROOF
 PLAN UNDER THE COMPONENT AND CLADDING PRESSURE ZONES
 TABLE. THIS NOTE CONTRADICTS THE NAIL SPACING
 SPECIFICATIONS SHOWN ON THE COMPONENT AND CLADDING
 PRESSURE ZONES TABLE. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS.
  
 5-LOT DRAINAGE
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING:
 R401.3 FBC-RESIDENTIAL.
 SEC. 107.2.5 CITY AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
  
 6- REVISE ENERGY CALCULATIONS SUBMITTED:
 (NOTE: BUILDING ORIENTATION AFFECTS THE ENERGY
 CALCULATIONS. NEED TO COORDINATE WITH ITEM #1 ABOVE).
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF
 FORM. PROVIDE CORRECT ADDRESS AND OWNER'S NAME, PROVIDE
 NAME OF BUILDER, PERMITTING OFFICE AND JURISDICTION
 NUMBER (THIS JURISDICTION IS 604700).
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 C) DOORS INFORMATION ON PAGE 3 OF 4 IS INCORRECT.
 (COORDINATE WITH ITEM #1 ABOVE).
 THIS BUILDING IS FACING CARVER AVE. THESE DOORS ARE
 LOCATED IN THE FRONT AND REAR OF BUILDING. SEE
 SURVEY/SITE PLAN AND FLOOR PLAN AND REVISE AS REQUIRED.
 . THEREFORE, THE CORRECT ORIENTATION IS WEST AND EAST.
 REVISE AS REQUIRED.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 D)WINDOWS INFORMATION ON PAGE 3 OF 4 IS INCORRECT.
 (COORDINATE WITH ITEM #1 ABOVE).
 THIS BUILDING IS FACING CARVER AVE. SEE SURVEY/SITE
 PLAN AND FLOOR PLAN AND REVISE AS REQUIRED. THERE ARE
 NO WINDOWS ON THE SOUTH SIDE.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION.
  
 E)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  