Plan Review Notes
Plan Review Notes For Permit 21041091
Permit Number 21041091
Review Stop B
Sequence Number 3
Notes
Date Text
2021-10-12 08:39:31ADD RESTROOM
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE PER FBC
 CHAPTER 6
 2) PLEASE STATE "REFLECTIVE SURFACE" - PLEASE SHOW THE
 MAXIMUM HEIGHT FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACE OF THE ACCESSIBLE RESTROOM MIRROR TO
 COMPLY WITH FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 3) TO AVOID INCORRECT PLACEMENT - PLEASE SHOW THE
 TOILET REAR GRAB BAR PLACEMENT DIMENSIONS FROM THE
 CENTER OF THE TOILET TO COMPLY WITH FBC A 604.5.2 REAR
 WALL.
 THE REAR WALL GRAB BAR SHALL BE 36 INCHES (915 MM) LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES (305 MM) MINIMUM ON ONE SIDE AND 24
 INCHES (610 MM) MINIMUM ON THE OTHER SIDE.
  
  
  