2021-06-09 13:23:11 | ADD RESTROOM |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE PER FBC |
| CHAPTER 6 |
| 2) PLEASE SHOW THE MAXIMUM HEIGHT FROM THE FINISHED |
| FLOOR TO THE REFLECTIVE SURFACE OF THE ACCESSIBLE |
| RESTROOM MIRROR TO COMPLY WITH FBC A603.3 MIRRORS. |
| MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL |
| BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING |
| SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND. |
| 3) PLEASE SHOW THE TOILET REAR GRAB BAR PLACEMENT |
| DIMENSIONS FROM THE CENTER OF THE TOILET TO COMPLY WITH |
| FBC A604.5.2 |
| 4) PLEASE SHOW THE MAXIMUM GRAB BAR HEIGHT FROM THE |
| FINISHED FLOOR TO THE TOP OF THE GRIPPING SURFACE PER |
| FBC A609.4 POSITION OF GRAB BARS. |
| GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION, |
| 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM) |
| MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF |
| THE GRIPPING SURFACE, |
| 5) PLEASE SHOW THE TOILET PAPER DISPENSER LOCATION FROM |
| THE FRONT OF THE TOILET TO COMPLY WITH FBC |
| A604.7DISPENSERS. |
| TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND |
| SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 |
| MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO |
| THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE |
| DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48 |
| INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND |
| SHALL NOT BE LOCATED BEHIND GRAB BARS. |
| 6) PLEASE SHOW THE ACCESSIBLE RESTROOM DOOR SWING TO |
| COMPLY WITH FBC A603.2.3 DOOR SWING. |
| DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| EXCEPTION "WHERE THE TOILET ROOM OR BATHING ROOM IS FOR |
| INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH |
| 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE |
| DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE |
| CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY |
| FIXTURE." PLEASE SHOW THE REQUIRED FLOOR SPACE FOR THIS |
| EXCEPTION. |
| |