Plan Review Notes
Plan Review Notes For Permit 21041091
Permit Number 21041091
Review Stop B
Sequence Number 1
Notes
Date Text
2021-06-09 13:23:11ADD RESTROOM
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENTS
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE PER FBC
 CHAPTER 6
 2) PLEASE SHOW THE MAXIMUM HEIGHT FROM THE FINISHED
 FLOOR TO THE REFLECTIVE SURFACE OF THE ACCESSIBLE
 RESTROOM MIRROR TO COMPLY WITH FBC A603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
 3) PLEASE SHOW THE TOILET REAR GRAB BAR PLACEMENT
 DIMENSIONS FROM THE CENTER OF THE TOILET TO COMPLY WITH
 FBC A604.5.2
 4) PLEASE SHOW THE MAXIMUM GRAB BAR HEIGHT FROM THE
 FINISHED FLOOR TO THE TOP OF THE GRIPPING SURFACE PER
 FBC A609.4 POSITION OF GRAB BARS.
 GRAB BARS SHALL BE INSTALLED IN A HORIZONTAL POSITION,
 33 INCHES (840 MM) MINIMUM AND 36 INCHES (915 MM)
 MAXIMUM ABOVE THE FINISH FLOOR MEASURED TO THE TOP OF
 THE GRIPPING SURFACE,
 5) PLEASE SHOW THE TOILET PAPER DISPENSER LOCATION FROM
 THE FRONT OF THE TOILET TO COMPLY WITH FBC
 A604.7DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER. THE OUTLET OF THE
 DISPENSER SHALL BE 15 INCHES (380 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR AND
 SHALL NOT BE LOCATED BEHIND GRAB BARS.
 6) PLEASE SHOW THE ACCESSIBLE RESTROOM DOOR SWING TO
 COMPLY WITH FBC A603.2.3 DOOR SWING.
 DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR
 CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE
 PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE.
 EXCEPTION "WHERE THE TOILET ROOM OR BATHING ROOM IS FOR
 INDIVIDUAL USE AND A CLEAR FLOOR SPACE COMPLYING WITH
 305.3 IS PROVIDED WITHIN THE ROOM BEYOND THE ARC OF THE
 DOOR SWING, DOORS SHALL BE PERMITTED TO SWING INTO THE
 CLEAR FLOOR SPACE OR CLEARANCE REQUIRED FOR ANY
 FIXTURE." PLEASE SHOW THE REQUIRED FLOOR SPACE FOR THIS
 EXCEPTION.
  