Plan Review Notes For Permit 21041080 |
Permit Number |
21041080 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2021-05-11 10:06:41 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | NFPA 70 2017 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | RISER SHOWS 2/0'A FEEDING THE LOADS, BECAUSE THERE IS 2 | | PANELS THE FEEDER IS NOT FEEDING THE ENTIRE LOAD SO | | 3/0'S WILL BE REQUIRED. 310.15(B)(7)(2) | | | | 310.15(B)(7)(2) FOR A FEEDER RATED 100 THROUGH 400 | | AMPERES, THE FEEDER CONDUCTORS SUPPLYING THE ENTIRE | | LOAD ASSOCIATED WITH A ONE-FAMILY DWELLING, OR THE | | FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED | | WITH AN INDIVIDUAL DWELLING UNIT IN A TWO-FAMILY OR | | MULTIFAMILY DWELLING, SHALL BE PERMITTED TO HAVE AN | | AMPACITY NOT LESS THAN 83 PERCENT OF THE FEEDER RATING. |
|