2021-05-11 10:06:41ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS 2/0'A FEEDING THE LOADS, BECAUSE THERE IS 2
 PANELS THE FEEDER IS NOT FEEDING THE ENTIRE LOAD SO
 3/0'S WILL BE REQUIRED. 310.15(B)(7)(2)
  
 310.15(B)(7)(2) FOR A FEEDER RATED 100 THROUGH 400
 AMPERES, THE FEEDER CONDUCTORS SUPPLYING THE ENTIRE
 LOAD ASSOCIATED WITH A ONE-FAMILY DWELLING, OR THE
 FEEDER CONDUCTORS SUPPLYING THE ENTIRE LOAD ASSOCIATED
 WITH AN INDIVIDUAL DWELLING UNIT IN A TWO-FAMILY OR
 MULTIFAMILY DWELLING, SHALL BE PERMITTED TO HAVE AN
 AMPACITY NOT LESS THAN 83 PERCENT OF THE FEEDER RATING.