2021-07-07 11:31:17 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING / PREVIOUS COMMENTS WERE NOT | | ADDRESSED | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) NOT COMPLIED. THE GENERATOR PAD DRAWING THAT WAS | | SUBMITTED REFERENCES THE FBC SIXTH EDITION (2017) AND | | ASCE 7-10. THE FBC SEVENTH EDITION (2020) WENT INTO | | EFFECT ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED | | FOR ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH | | AND REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE | | 7-16. FS CHAPTER 553 | | | | 2) NOT COMPLIED. THIS PROJECT IS LOCATED IN A SPECIAL | | FLOOD HAZARD AREA. THE GENERATOR AND ALL RELATED | | EQUIPMENT THAT IS SUBJECT TO DAMAGE FROM FLOOD WATERS | | ARE REQUIRED TO BE ELEVATED TO OR ABOVE THE FINISH | | FLOOR OF THE HABITABLE AREA OF THE EXISTING HOME. FBC | | R-322 |
|