Plan Review Notes
Plan Review Notes For Permit 21041075
Permit Number 21041075
Review Stop B
Sequence Number 2
Notes
Date Text
2021-07-07 11:31:17PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING / PREVIOUS COMMENTS WERE NOT
 ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) NOT COMPLIED. THE GENERATOR PAD DRAWING THAT WAS
 SUBMITTED REFERENCES THE FBC SIXTH EDITION (2017) AND
 ASCE 7-10. THE FBC SEVENTH EDITION (2020) WENT INTO
 EFFECT ON DECEMBER 31, 2020. ALL NEW PERMITS APPLIED
 FOR ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH
 AND REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE
 7-16. FS CHAPTER 553
  
 2) NOT COMPLIED. THIS PROJECT IS LOCATED IN A SPECIAL
 FLOOD HAZARD AREA. THE GENERATOR AND ALL RELATED
 EQUIPMENT THAT IS SUBJECT TO DAMAGE FROM FLOOD WATERS
 ARE REQUIRED TO BE ELEVATED TO OR ABOVE THE FINISH
 FLOOR OF THE HABITABLE AREA OF THE EXISTING HOME. FBC
 R-322