Text |
2021-05-11 08:38:06 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE GENERATOR PAD DRAWING THAT WAS SUBMITTED | | REFERENCES THE FBC SIXTH EDITION (2017) AND ASCE 7-10. | | THE FBC SEVENTH EDITION (2020) WENT INTO EFFECT ON | | DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR | | AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND | | REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE 7-16. | | FS CHAPTER 553 | | | | 2) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD | | AREA. THE GENERATOR AND ALL RELATED EQUIPMENT THAT IS | | SUBJECT TO DAMAGE FROM FLOOD WATERS ARE REQUIRED TO BE | | ELEVATED TO OR ABOVE THE FINISH FLOOR OF THE HABITABLE | | AREA OF THE EXISTING HOME. FBC R-322 |
|