Plan Review Notes
Plan Review Notes For Permit 21041075
Permit Number 21041075
Review Stop B
Sequence Number 1
Notes
Date Text
2021-05-11 08:38:06PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE GENERATOR PAD DRAWING THAT WAS SUBMITTED
 REFERENCES THE FBC SIXTH EDITION (2017) AND ASCE 7-10.
 THE FBC SEVENTH EDITION (2020) WENT INTO EFFECT ON
 DECEMBER 31, 2020. ALL NEW PERMITS APPLIED FOR ON OR
 AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE 2020 FBC SEVENTH EDITION AND ASCE 7-16.
 FS CHAPTER 553
  
 2) THIS PROJECT IS LOCATED IN A SPECIAL FLOOD HAZARD
 AREA. THE GENERATOR AND ALL RELATED EQUIPMENT THAT IS
 SUBJECT TO DAMAGE FROM FLOOD WATERS ARE REQUIRED TO BE
 ELEVATED TO OR ABOVE THE FINISH FLOOR OF THE HABITABLE
 AREA OF THE EXISTING HOME. FBC R-322