Plan Review Notes
Plan Review Notes For Permit 21041058
Permit Number 21041058
Review Stop P
Sequence Number 1
Notes
Date Text
2021-09-09 17:33:321ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21041058
 9/9/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE IDENTIFY THE PROPOSED USES OF THE SHELL
 SPACES- SECTION 107.2.1 WPB.
  
 2) SHEET P301: PLEASE NOTE THAT INSTALLATION OF THE
 GREASE INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT AND
 WILL REQUIRE A SEPARATE PRIMARY PERMIT APPLICATION AND
 PLAN SUBMITTALS- SECTION 105.1 & 107.2.1 WPB. FOR THE
 PURPOSES OF THIS REVIEW, AND IN ACCORDANCE WITH
 SECTIONS 1003.3.1- 1003.3.4 FBC P PLEASE PROVIDE:
 A) INTERCEPTOR SIZING CALCULATIONS.
 C) THE LOCATION OF THE SAMPLING PORT AND PROVIDE AN
 INSTALLATION DETAIL.
 D) APPROVED TRAFFIC LID SPECIFICATIONS TO PROTECT THE
 INTERCEPTOR, SAMPLING PORT ACCESS, AND CLEANOUT ACCESS
 FROM VEHICLE DAMAGE.
  
 3) P301 & P401: PLEASE PROVIDE THE CIVIL PLANS FOR
 WATER SERVICE AND SANITARY SEWER CONTINUATIONS AS
 REFERENCED IN THE NOTES- SECTION 107.2.1 WPB.
  
 4) P301: PLEASE NOTE THAT INDIVIDUAL SEPARATE PERMITS
 ARE REQUIRED FOR INSTALLATION OF THE POTABLE WATER
 SERVICE BACKFLOW PREVENTER, AND THE IRRIGATION SYSTEM
 BACKFLOW PREVENTER. A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN SEPARATE PERMITS FOR INSTALLATION OF THE
 DEVICES IN ACCORDANCE WITH SECTION 105.1WPB AND SEC.
 90-33 WPB CODE OF ORDINANCES. THE DEVICES SHALL BE
 TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION.
  
 5) P301 & P601: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES- SECTION 419.5 FBC P.
  
 6) P301 & P401: REFER TO TABLE C404.5.1 FBC EC- THE
 MAXIMUM PIPING LENGTH OF 2 FT. FROM THE HEATED WATER
 SOURCE TO THE LAVATORIES IS EXCEEDED WHICH WILL REQUIRE
 INSTALLATION OF A RECIRCULATION PUMP OR POINT OF USE
 WATER HEATERS AT THE LAVS.
  
 7) A2.0A: PLEASE SEE THE FBC ACC CODE SECTIONS BELOW
 AND REVISE THE DRAWINGS ACCORDINGLY.
  
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
  
 B) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
  
 C) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
  
 D) TURNING SPACE DIAMETERS- SECTION 304.3.
  
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. THE REAR GRAB BAR POSITION
 SHALL BE DEPICTED IN COMPLIANCE WITH FIGURE 604.5.2.
  
 F) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
  
 G) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
  
 H) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
  
 I) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 7) A2.0A: DETAIL 9 SHOWS THE MOP SINK WALL SURROUND TO
 BE PAINTED DRYWALL WHICH IS NOT IN COMPLIANCE WITH
 SECTION 1210.2.2 FBC P.
  
 8) P701: REVISE THE WATER HEATER DETAIL TO INCLUDE THE
 LOCATION OF THE REQUIRED THERMAL EXPANSION TANK-
 SECTION 607.3 FBC P.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  