2021-05-27 15:23:53 | REVISION |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENTS |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) DRAWING A6.0 APPEARS TO BE A PREVIOUS PLAN THAT |
| SHOWS DOOR PRODUCT APPROVALS WHICH WERE NOT APPROVED. |
| 2) PLEASE SHOW STAIR HANDRAIL EXTENSIONS TOP AND BOTTOM |
| TO COMPLY WITH FBC 1014.6 HANDRAIL EXTENSIONS. |
| HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING |
| SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN |
| ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS |
| ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL |
| EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) |
| BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE |
| DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. AT RAMPS |
| WHERE HANDRAILS ARE NOT CONTINUOUS BETWEEN RUNS, THE |
| HANDRAILS SHALL EXTEND HORIZONTALLY ABOVE THE LANDING |
| 12 INCHES (305 MM) MINIMUM BEYOND THE TOP AND BOTTOM OF |
| RAMP RUNS. THE EXTENSIONS OF HANDRAILS SHALL BE IN THE |
| SAME DIRECTION OF THE FLIGHTS OF STAIRS AT STAIRWAYS |
| AND THE RAMP RUNS AT RAMPS. |
| 3) DRAWING A2.0 APPEARS TO BE A PREVIOUS PLAN WHICH |
| SHOWS EXTERIOR CORRIDOR BLOCKED WITH DOORS THAT OPEN |
| OUT BETWEEN THE UNITS FBC 1005.7.1 DOORS. |
| DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED |
| WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY |
| POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE |
| THAN ONE-HALF. |