Plan Review Notes
Plan Review Notes For Permit 21041043
Permit Number 21041043
Review Stop G
Sequence Number 3
Notes
Date Text
2021-08-09 15:05:223RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041043
 8/9/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE
 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER
 CLARIFICATION.
  
 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 304.1 FBC FG. THE REVISED CALCS ARE USING THE EQUATION
 FOUND IN SECTION 304.5.2 WHICH CAN ONLY BE USED WHEN
 THERE IS A KNOWN AIR INFILTRATION RATE LESS THAN .40
 AIR CHANGES PER HOUR (ACH). THE CALCULATIONS PROVIDED
 ARE USING AN ACH OF 17.6. THE CALCULATION IS ALSO USING
 700 CFMS OF O/A AS THE BASIS OF THE ACH, HOWEVER THE
 AIR IS BEING SUPPLIED MECHANICALLY AS OPPOSED TO
 INFILTRATION. IF USING MECHANICAL AIR PLEASE REFER TO
 SECTION 304.9 AND PROVIDE THE CALCULATION. PLEASE
 REVIEW SECTION 304.5.1 BELOW:
 THE REQUIRED VOLUME OF INDOOR AIR SHALL BE DETERMINED
 IN ACCORDANCE WITH SECTION 304.5.1 OR 304.5.2, EXCEPT
 THAT WHERE THE AIR INFILTRATION RATE IS KNOWN TO BE
 LESS THAN 0.40 AIR CHANGES PER HOUR (ACH), SECTION
 304.5.2 SHALL BE USED. THE TOTAL REQUIRED VOLUME SHALL
 BE THE SUM OF THE REQUIRED VOLUME CALCULATED FOR ALL
 APPLIANCES LOCATED WITHIN THE SPACE. ROOMS
 COMMUNICATING DIRECTLY WITH THE SPACE IN WHICH THE
 APPLIANCES ARE INSTALLED THROUGH OPENINGS NOT FURNISHED
 WITH DOORS, AND THROUGH COMBUSTION AIR OPENINGS SIZED
 AND LOCATED IN ACCORDANCE WITH SECTION 304.5.3, ARE
 CONSIDERED TO BE PART OF THE REQUIRED VOLUME.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719