Plan Review Notes
Plan Review Notes For Permit 21041043
Permit Number 21041043
Review Stop P
Sequence Number 2
Notes
Date Text
2021-07-16 14:55:582ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21041043
 7/16/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #2, 3D, 5,
 & 9 ARE LISTED BELOW.
  
 2) FAILED. SHEET A2.1.1: PROVIDE THE KNEE AND TOE
 CLEARANCES FOR THE SINKS- SECTIONS 606.2 & 306.1 FBC
 ACC. REFER TO FIGURES 306.2 & 306.3 AND PROVIDE THE
 ACTUAL CLEARANCE MEASUREMENT IN THE DETAIL.
  
 3D) FAILED. PROVIDE A SITE AND SURVEY PLAN SHOWING THE
 LOCATION OF THE NEW GREASE INTERCEPTOR. IF TO BE
 INSTALLED IN A PARKING LOT OR DRIVE AREA, A HEAVY-DUTY
 TRAFFIC LID WILL BE REQUIRED- SECTION 107.2.1 WPB AND
 1003.3.5 FBC P. PLEASE REVISE KEYNOTES 1-3 ON P5.1 TO
 CLEARLY INDICATE THE WORK DESCRIBED WILL BE UNDER
 SEPARATE PERMIT.
  
 5) FAILED. P2.1: NONCOMPLIANT SANITARY WET VENT- TWO
 WATER CLOSETS UPSTREAM OF THE DRY VENT CONNECTION-
 SECTION 912.2.1 FBC P. NOT CORRECTED.
  
 9) FAILED. P5.1: KEY NOTES #1 & 3 SPECIFY CIVIL PLANS
 FOR LOCATIONS OF THE SEWER LATERAL, AND NEW WATER METER
 AND BACKFLOW PREVENTER. PLEASE PROVIDE THE PLANS-
 SECTION 107.2.1. PLEASE NOTE THAT A SEPARATE PERMIT IS
 REQUIRED FOR INSTALLATION OF THE POTABLE WATER SERVICE
 BACKFLOW ASSEMBLY- A FL. LICENSED PLUMBING CONTRACTOR
 SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE
 BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB
 AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL
 BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT
 PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT.
 PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS
 DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. PLEASE
 REVISE KEYNOTES 1-3 ON P5.1 TO CLEARLY INDICATE THE
 WORK DESCRIBED WILL BE UNDER SEPARATE PERMIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719