2021-07-16 14:55:58 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 21041043 |
| 7/16/2021 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS #2, 3D, 5, |
| & 9 ARE LISTED BELOW. |
| |
| 2) FAILED. SHEET A2.1.1: PROVIDE THE KNEE AND TOE |
| CLEARANCES FOR THE SINKS- SECTIONS 606.2 & 306.1 FBC |
| ACC. REFER TO FIGURES 306.2 & 306.3 AND PROVIDE THE |
| ACTUAL CLEARANCE MEASUREMENT IN THE DETAIL. |
| |
| 3D) FAILED. PROVIDE A SITE AND SURVEY PLAN SHOWING THE |
| LOCATION OF THE NEW GREASE INTERCEPTOR. IF TO BE |
| INSTALLED IN A PARKING LOT OR DRIVE AREA, A HEAVY-DUTY |
| TRAFFIC LID WILL BE REQUIRED- SECTION 107.2.1 WPB AND |
| 1003.3.5 FBC P. PLEASE REVISE KEYNOTES 1-3 ON P5.1 TO |
| CLEARLY INDICATE THE WORK DESCRIBED WILL BE UNDER |
| SEPARATE PERMIT. |
| |
| 5) FAILED. P2.1: NONCOMPLIANT SANITARY WET VENT- TWO |
| WATER CLOSETS UPSTREAM OF THE DRY VENT CONNECTION- |
| SECTION 912.2.1 FBC P. NOT CORRECTED. |
| |
| 9) FAILED. P5.1: KEY NOTES #1 & 3 SPECIFY CIVIL PLANS |
| FOR LOCATIONS OF THE SEWER LATERAL, AND NEW WATER METER |
| AND BACKFLOW PREVENTER. PLEASE PROVIDE THE PLANS- |
| SECTION 107.2.1. PLEASE NOTE THAT A SEPARATE PERMIT IS |
| REQUIRED FOR INSTALLATION OF THE POTABLE WATER SERVICE |
| BACKFLOW ASSEMBLY- A FL. LICENSED PLUMBING CONTRACTOR |
| SHALL OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. PLEASE |
| REVISE KEYNOTES 1-3 ON P5.1 TO CLEARLY INDICATE THE |
| WORK DESCRIBED WILL BE UNDER SEPARATE PERMIT. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |