2021-08-09 15:04:052ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041043
 7/16/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE
 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER
 CLARIFICATION.
  
 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 304.1 FBC FG. THE CALCULATIONS ON THE TOP LEFT OF THE
 SHEET APPEAR TO INDICATE A DEFICIENT AMOUNT OF CUBIC FT
 PROVIDED FOR INDOOR COMBUSTION AIR. PLEASE NOTE THAT
 THE VOLUME OF THE DINING ROOM CANNOT BE USED UNLESS
 OPENINGS SIZED IN ACCORDANCE WITH SECTION 304.5.3 FBC
 FG ARE PROVIDED. THE CALCULATION AT THE BOTTOM LEFT OF
 THE PAGE IS INDICATING 1000 CFMS OF O/A HOWEVER THE
 KITCHEN AC SYSTEM SHOWN ON SHEET M.6.1 INDICATES 700
 CFMS. PLEASE PROVIDE REVISED CALCULATIONS.
 NEW COMMENT.
  
 1) SHEETS P3.1 & P5.1: THE REQUESTED SPECS FOR THE
 GAS-FIRED TANKLESS WATER WERE NOT SUBMITTED AND MAY BE
 DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB.
 PLEASE CLEARLY SHOW THE LOCATIONS OF THE NEW METER AND
 THE WATER HEATER WITH ALL REQUIRED CLEARANCES INCLUDING
 THE DOOR OPENING INTO THE KITCHEN- SECTION 624.1 FBC
 FG. FOR CONDENSING TYPE WATER HEATER SHOW HOPW
 CONDENSATE FROM THE UNIT WILL BE DISCHARGED TO AN
 APPROVED PLACE OF DISPOSAL- SECTIONS 307.2 & 307.3 FBC
 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
2021-07-16 14:54:292ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21041043
 7/16/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE
 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER
 CLARIFICATION.
  
 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS
 AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION
 304.1 FBC FG. THE CALCULATIONS ON THE TOP LEFT OF THE
 SHEET APPEAR TO INDICATE A DEFICIENT AMOUNT OF CUBIC FT
 PROVIDED FOR INDOOR COMBUSTION AIR. PLEASE NOTE THAT
 THE VOLUME OF THE DINING ROOM CANNOT BE USED UNLESS
 OPENINGS SIZED IN ACCORDANCE WITH SECTION 304.5.3 FBC
 FG ARE PROVIDED. THE CALCULATION AT THE BOTTOM LEFT OF
 THE PAGE IS INDICATING 1000 CFMS OF O/A HOWEVER THE
 KITCHEN AC SYSTEM SHOWN ON SHEET M.6.1 INDICATES 700
 CFMS. PLEASE PROVIDE REVISED CALCULATIONS.
 NEW COMMENT.
  
 1) SHEETS P3.1 & P5.1: THE REQUESTED SPECS FOR THE
 GAS-FIRED TANKLESS WATER WERE NOT SUBMITTED AND MAY BE
 DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB.
 PLEASE CLEARLY SHOW THE LOCATIONS OF THE NEW METER AND
 THE WATER HEATER WITH ALL REQUIRED CLEARANCES INCLUDING
 THE DOOR OPENING INTO THE KITCHEN- SECTION 624.1 FBC
 FG. FOR CONDENSING TYPE WATER HEATER SHOW HOPW
 CONDENSATE FROM THE UNIT WILL BE DISCHARGED TO AN
 APPROVED PLACE OF DISPOSAL- SECTIONS 307.2 & 307.3 FBC
 FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  