2021-08-09 15:04:05 | 2ND REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21041043 |
| 7/16/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE |
| 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER |
| CLARIFICATION. |
| |
| 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS |
| AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION |
| 304.1 FBC FG. THE CALCULATIONS ON THE TOP LEFT OF THE |
| SHEET APPEAR TO INDICATE A DEFICIENT AMOUNT OF CUBIC FT |
| PROVIDED FOR INDOOR COMBUSTION AIR. PLEASE NOTE THAT |
| THE VOLUME OF THE DINING ROOM CANNOT BE USED UNLESS |
| OPENINGS SIZED IN ACCORDANCE WITH SECTION 304.5.3 FBC |
| FG ARE PROVIDED. THE CALCULATION AT THE BOTTOM LEFT OF |
| THE PAGE IS INDICATING 1000 CFMS OF O/A HOWEVER THE |
| KITCHEN AC SYSTEM SHOWN ON SHEET M.6.1 INDICATES 700 |
| CFMS. PLEASE PROVIDE REVISED CALCULATIONS. |
| NEW COMMENT. |
| |
| 1) SHEETS P3.1 & P5.1: THE REQUESTED SPECS FOR THE |
| GAS-FIRED TANKLESS WATER WERE NOT SUBMITTED AND MAY BE |
| DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. |
| PLEASE CLEARLY SHOW THE LOCATIONS OF THE NEW METER AND |
| THE WATER HEATER WITH ALL REQUIRED CLEARANCES INCLUDING |
| THE DOOR OPENING INTO THE KITCHEN- SECTION 624.1 FBC |
| FG. FOR CONDENSING TYPE WATER HEATER SHOW HOPW |
| CONDENSATE FROM THE UNIT WILL BE DISCHARGED TO AN |
| APPROVED PLACE OF DISPOSAL- SECTIONS 307.2 & 307.3 FBC |
| FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL/PLUMBING PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
2021-07-16 14:54:29 | 2ND REVIEW FBC-2020 FUEL GAS |
| PERMIT- 21041043 |
| 7/16/2021 |
| |
| CODES IN EFFECT: |
| FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| 2020 |
| FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENT #4 FROM THE |
| 1ST REVIEW IS LISTED BELOW WITH NOTES ADDED FOR FURTHER |
| CLARIFICATION. |
| |
| 4) FAILED. P5.1: PROVIDE COMBUSTION AIR CALCULATIONS |
| AND INDICATE HOW THE AIR WILL BE PROVIDED- SECTION |
| 304.1 FBC FG. THE CALCULATIONS ON THE TOP LEFT OF THE |
| SHEET APPEAR TO INDICATE A DEFICIENT AMOUNT OF CUBIC FT |
| PROVIDED FOR INDOOR COMBUSTION AIR. PLEASE NOTE THAT |
| THE VOLUME OF THE DINING ROOM CANNOT BE USED UNLESS |
| OPENINGS SIZED IN ACCORDANCE WITH SECTION 304.5.3 FBC |
| FG ARE PROVIDED. THE CALCULATION AT THE BOTTOM LEFT OF |
| THE PAGE IS INDICATING 1000 CFMS OF O/A HOWEVER THE |
| KITCHEN AC SYSTEM SHOWN ON SHEET M.6.1 INDICATES 700 |
| CFMS. PLEASE PROVIDE REVISED CALCULATIONS. |
| NEW COMMENT. |
| |
| 1) SHEETS P3.1 & P5.1: THE REQUESTED SPECS FOR THE |
| GAS-FIRED TANKLESS WATER WERE NOT SUBMITTED AND MAY BE |
| DEFERRED IN ACCORDANCE WITH SECTION 107.3.4.1 WPB. |
| PLEASE CLEARLY SHOW THE LOCATIONS OF THE NEW METER AND |
| THE WATER HEATER WITH ALL REQUIRED CLEARANCES INCLUDING |
| THE DOOR OPENING INTO THE KITCHEN- SECTION 624.1 FBC |
| FG. FOR CONDENSING TYPE WATER HEATER SHOW HOPW |
| CONDENSATE FROM THE UNIT WILL BE DISCHARGED TO AN |
| APPROVED PLACE OF DISPOSAL- SECTIONS 307.2 & 307.3 FBC |
| FG. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |